Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR08-00047
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 700 S CLEARWATER LN
Project NameCLEARWATER BLDG
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a new, required manual fire alarm system in an existing non sprinklered building. The new fire alarm system includes manual pull stations at all exits, induct smoke detection for fire smoke damper closure, HVAC system monitoring, remote annunciator and audible visual notification in public and common use areas. Building permit BLD07-01932 is to remodel the entire 29,125 sq.ft. two story office building for a new office tenant per approved plans. No exterior changes under this permit. Work includes select interior demolition; new non-bearing walls to create offices, support and access / egress paths on both floors; Construct and/or repair a 1-hour fire-rated, tunneled exit corridor system to create / complete a rated exit corridor on both levels; to upgrade interior finishes, ceiling systems, millwork, electrical, mechanical, plumbing and alarm systems to meet tenant needs and to comply with current adopted codes and ordinances. drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/8/2009 DONE
Plans taken to records to scan
INSP-Final Inspection7/15/20087/16/20087/16/2008APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection7/14/20087/15/20087/15/2008AFAIL
DetailsTroy Cobbley
The elevator did not recall to the second floor when the mechanical room smoke detector was activated. The other recall functions worked.
CHANGE STATUS TO (ISS)  7/15/2008 DONE
was final by mistake - it was failed on the 15th
INSP-Final Inspection7/14/20087/14/20087/14/2008PCANC
DetailsTroy Cobbley
Cancelled due to time constraints.
INSP-Final Inspection6/30/20086/30/20086/30/2008PPART
DetailsForrest France
Temp. okayed with D. Hanneman's permission pending completion of the elevator controls-no elevator use allowed until upgrade work is finished, tested and related fire alarm permit finaled.
INSP-Final Inspection6/26/20086/27/20086/27/2008APART
DetailsForrest France
Final pending completion of elevator controls to enable testing and functionality of recall, shunt trip, fire hat, etc. Remainder of items listed on the correction notice are finished, as-builts accepted. NFPA 72 record of completion forms have not been signed pending elevator testing.
INSP-Alarm Testing6/23/20086/23/20086/23/2008APART
DetailsForrest France
See correction notice for list of items in need of revision.
INSP-Final Inspection6/19/20086/20/20086/20/2008APART
DetailsForrest France
New system fire alarm testing completed today including the FACP, NAC, RA, notification, initiation, dampers, HVAC controls and clean agent fire suppression panel interconnect. Elevator is not yet completed to enable functional testing of recall, shunt trip, SD's etc. Noted areas on the approved plan set in need of revision including one a/v to be added, adjust cd at one device, provide signage at the door to the FACP room per note #30, need as-built plans for documentation of moved EOL's and correct location for RTU's including clean agent monitoring, will test elevator controls when completed, mag locks at egress doors drop on FA with the exception of two doors not yet installed, dB at the womens and mens restrooms are possibly over max.110 allowed-will test at next site visit, map at the panel is acceptable.
FIR-Aging Inspection4/23/20084/23/20084/23/2008 DONE
DetailsForrest France
Under construction, work in progress.
Issue and Print Permit  1/23/2008 DONE
Plan assigned to (Mike)1/17/2008 1/22/2008 PASS
DetailsMichael Timmerman
1/22/2008 11:09:28 MWT - activity updated through activity FIRA22 from case FIR08-00047.
PLANS/APPL TAKEN TO FRONT DESK  1/22/2008 DONE
Ready For Issue
Inspection Record Card- Fire1/22/2008 1/22/2008 DONE
DetailsPatricia Smith
Telephone call  1/22/2008 DONE
left vm for mike brown at ###-#### - permit ready and fees given
Permit Ready to Issue  1/22/2008 DONE
Alarm Plan Check1/18/2008 1/18/2008 PASS
DetailsMichael Timmerman
Fire Alarm Review 1st
Application received  1/17/2008