Permit Information
Permit NumberFIR08-00060
StatusFinaled
Name ADT SECURITY SERVICES INC
Site Address 300 N MILWAUKEE ST
Project NameJC PENNEY
Customer Number 
ePlanReview 
Description
This fire alarm permit is to remodel the support area offices and some sales areas for JC Penny's BLD07-00626. Install and relocate fire alarm device due to the construction of new interior partitions.

MODIFICATION: 08-07-08 the originally submitted plans did not show the correct layout. New plans and submittals have been provided showing the accurate floor plan and device layout.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/8/2009 DONE
plans taken to records for scanning
INSP-Final Inspection8/18/20088/19/20088/19/2008APASS
DetailsTroy Cobbley
Permit finaled
(F) Reprint permit  8/8/2008 DONE
CHANGE STATUS TO (ISS)  8/8/2008 DONE
Plan assigned to (Stephanie)7/30/2008 8/7/2008 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check  8/7/2008 PASS
PLANS/APPL TAKEN TO FRONT DESK  8/7/2008 DONE
Inspection Record Card- Fire8/7/2008 8/7/2008 DONE
Details
Telephone call  8/7/2008 DONE
Details
t/c w dave whiting at ###-#### - permit ready - no fees
Permit Ready to Issue  8/7/2008 DONE
Details
Plan resubmittals received  7/30/2008  
DetailsStephanie L. Cobbley
Plan Modification: Recevied two copies of application, submittal binder, plan sheets 1 of 9, 2 of 9, 3 of 9, 4 of 9, 5 of 9, 6 of 9, 7 of 9, 8 of 9, 9 of 9, 1 of 2, 2 of 2, and two more copies of battery calcs; taken to Fire Review
Telephone call  7/23/2008 DONE
Scotty with ADT called stating that the fire alarm drawings originally submitted are not accurate. He stated that the floorplan submitted did not accurately show rooms and several walls, and that several devices were not mounted where the approved drawings had shown them to be. Scotty wanted to know if it had to be resubmitted or if the inspector could make a field approval. I let him know that there were too many inconsistencies to approve it in the field, that he would have to resubmit for a plan modification and have it approved prior to calling in an inspection. He indicated he would get that information submitted as soon as possible.
CHANGE STATUS TO (ISS)  7/17/2008  
already picked up??
Telephone call  7/17/2008 DONE
Spoke to Dave regarding the status of the project. He said it is still in progress.
Inspection Record Card- Fire1/31/2008 1/31/2008 DONE
DetailsPatricia Smith
Telephone call  1/31/2008 DONE
left vm for dave whiting at ###-#### - permit ready and fees given
Permit Ready to Issue  1/31/2008 DONE
Plan assigned to (Mike)1/24/2008 1/30/2008 DONE
DetailsKenneth R Roule
IFC 2006 NFPA 2007
PLANS/APPL TAKEN TO FRONT DESK  1/30/2008  
Application received  1/24/2008  
Case Summary  1/24/2008 DONE