Miscellaneous action | | | 4/25/2008 | | DONE |
|
|
|
Plans sent to records for scanning.
|
INSP-Final Inspection | 1/29/2008 | 1/30/2008 | 1/29/2008 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled. The additional pendant has been added.
|
Override - People Holds | | | 1/28/2008 | | |
|
|
|
|
Inspection Record Card- Fire | 1/28/2008 | | 1/28/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 1/28/2008 | | DONE |
|
|
|
left message w gary for steve batten at alloway elec. - ###-#### - permit ready and fees given
|
Override - People Holds | | | 1/28/2008 | | |
|
|
|
|
Permit Ready to Issue | | | 1/28/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/28/2008 | | |
|
|
|
|
Application received | | | 1/25/2008 | | |
|
|
|
|
Plan assigned to (Mike) | 1/25/2008 | | 1/25/2008 | | PASS |
Michael Timmerman
|
|
|
1/25/2008 16:23:39 MWT - activity updated through activity FIRA22 from case FIR08-00062.
|
Alarm Plan Check | 1/25/2008 | | 1/25/2008 | | PASS |
Michael Timmerman
|
|
|
Fire Alarm Quick Permit "Pass" This Fire Alarm Quick Permit is subject to field inspection and testing. An existing wall is being removed and is creating a large open area that may be corridor or work space. See note on the floor plans. An existing 15cd notification appliance may be required to be increased if this is open office area. Field verify. Also, the existing side of the tenant area has full coverage smoke detection the purpose is unclear. If it is used to close fire/smoke dampers then the area detection must be extended into the new tenant expansion and a new submittal will be required.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/25/2008 | | DONE |
|
|
|
Ready for Issue
|