Miscellaneous action | | | 6/4/2008 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 4/1/2008 | 4/1/2008 | 4/1/2008 | P | PASS |
Kenneth R Roule
|
|
|
Fire alarm inspection complete.KR
|
DOC - Permit Finaled | | | 4/1/2008 | | DONE |
|
|
|
permit finaled
|
INSP-Alarm Testing | 3/28/2008 | 3/31/2008 | 3/31/2008 | A | PASS |
Forrest France
|
|
|
Fire alarm inspection complete.KR
|
Override - Parcel Holds | 3/28/2008 | 1/1/1900 | 3/28/2008 | | |
|
|
|
does not apply
|
INSP-Final Inspection | 3/26/2008 | 3/27/2008 | 3/27/2008 | P | FAIL |
Forrest France
|
|
|
Drawings do not match floorplan, one workroom not shown on plans will need notification, noted overspaced strobes at three locations, one av has been deleted due to room changes, no devices tested at this time.
|
Override - Parcel Holds | 3/26/2008 | 1/1/1900 | 3/26/2008 | | |
|
|
|
not in the plan mod area
|
Plan assigned to (Mike) | 2/1/2008 | | 2/11/2008 | | DONE |
Kenneth R Roule
|
|
|
IFC 2006, NFPA 2007
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/11/2008 | | |
|
|
|
|
Inspection Record Card- Fire | 2/11/2008 | | 2/11/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 2/11/2008 | | DONE |
|
|
|
t/c w kevin perez at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 2/11/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/11/2008 | | DONE |
|
|
|
|
Application received | | | 2/1/2008 | | |
|
|
|
|