Miscellaneous action | | | 6/4/2008 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 4/1/2008 | 4/1/2008 | 4/1/2008 | P | PASS |
Forrest France
|
|
|
|
DOC - Permit Finaled | | | 4/1/2008 | | |
|
|
|
permit finaled
|
INSP-Alarm Testing | 3/28/2008 | 3/31/2008 | 3/31/2008 | A | PASS |
Forrest France
|
|
|
Fire alarm inspection complete.KR
|
Miscellaneous action | | | 3/31/2008 | | DONE |
Scott Arellano
|
|
|
3/31/08 - The scope of work from BLD07-03236 (now voided) is now part of BLD07-03135. (KOWALIS & MACKEY - BODO BLDG #4 - STE 260) PLAN MODIFICATION - 3/21/08 - TO COMBINE UNIT #260 AND UNIT #270 INTO ONE SUITE, UNIT 260. TO VOID PERMIT BLD07-03236 AND COMBINE ALL WORK AND OCCUPANCY APPROVAL UNDER THIS PERMIT. PLAN MODIFICATION WILL INCREASE THE AREA AND OCCUPANT LOAD FOR UNIT #260. A 5' + HALLWAY WILL CONNECT THE TWO OFFICE AREAS TO BE ONE. ALL RED-LINED COMMENTS AND ATTACHED PLAN REVIEW CONDITIONS ARE STILL APPLICABLE TO THIS PROJECT UNLESS SPECIFICALLY MODIFIED AS PART OF THE PLAN MODIFICATION APPLICATION & MODIFIED PLANS.
|
Override - Parcel Holds | 3/28/2008 | 1/1/1900 | 3/28/2008 | | |
|
|
|
does not apply
|
INSP-Final Inspection | 3/26/2008 | 3/27/2008 | 3/27/2008 | P | FAIL |
Forrest France
|
|
|
Need to relocate or remove the smoke detector at the new nac panel, noted some overspaced notification devices, tenant floorplan has been modified to include an adjacent space-building permit is under review for approval. No alarm testing completed today.
|
Override - Parcel Holds | 3/26/2008 | 1/1/1900 | 3/26/2008 | | |
|
|
|
not in plan mod area
|
Plan assigned to (Mike) | 2/1/2008 | | 2/11/2008 | | PASS |
|
|
|
IFC2006, NFPA 2007
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/11/2008 | | |
|
|
|
|
Inspection Record Card- Fire | 2/11/2008 | | 2/11/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 2/11/2008 | | DONE |
|
|
|
t/c w kevin perez at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 2/11/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 2/11/2008 | | DONE |
|
|
|
|
Application received | | | 2/1/2008 | | |
|
|
|
|