Permit Information
Permit NumberFIR08-00103
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 323 W JEFFERSON ST
Project NameTHE JEFFERSON BLDG
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a new fire alarm system in a fully sprinklered R/2 occupancy consisting of 1st/2nd split level floor and 3rd thru 7th floors on top of an S/2 2-level 4 tiered parking garage. To include sprinkler monitoring, fire pump monitoring and elevator recall and shunt function.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/8/2009 DONE
plans taken to records for scanning
INSP-Final Inspection3/19/20093/20/20093/20/2009APASS
DetailsForrest France
Fire alarm permit approved for final.
Plan assigned to (Forrest)3/16/2009 3/16/2009 DONE
DetailsForrest France
Alarm Plan Check3/16/2009 3/16/2009 PASS
Details
Modified plans by R. Gobler approved per "red lined" plan annotations. No written comments.
PLANS/APPL TAKEN TO FRONT DESK  3/16/2009 DONE
Telephone call  3/16/2009 DONE
Details
left vm for robert gobler at ###-#### - permit ready to be picked (resubmittal)
Permit Ready to Issue  3/16/2009 DONE
Details
Inspection Record Card- Fire3/16/2009 3/16/2009 DONE
Details
CHANGE STATUS TO (ISS)  3/16/2009 DONE
(F) Reprint permit  3/16/2009 DONE
Plan assigned to (SAM)2/25/2009 3/9/2009 PEND
DetailsSam Rogers
3/9/09 - Met with Rober Guler and discussed plan discrepancies and omissions. He will make annotated corrections in "red" with his initials on all plan sets at the plan desk here in the PDS office and and return the corrected plans to the permit counter. Plans left at the front counter for him to obtain later this afternoon to make corrections.
Plan resubmittals received  2/25/2009  
Plan modification: Received application, three copies of submittal info binder, and plan sheets F0.0, F1.0, F1.1, F1.2, F1.3, F1.4, F1.5, F1.6, F1.7, F2.0 taken to Fire Review
INSP-Alarm Testing2/24/20092/24/20092/24/2009PDONE
DetailsTroy Cobbley
TRASH ROOM SMOKE DETECTOR Phone #: ###-#### Internet Inspection Request from: Robert Gobler
INSP-Alarm Testing2/24/20092/24/20092/24/2009ADONE
DetailsScott Arellano
Tested smoke door operation at exterior wall, located in garbage room. Tested satisfactory.
INSP-Final Inspection2/20/20092/20/20092/20/2009PPART
DetailsForrest France
Remainder of fire alarm testing completed satisfactory, noted corrections have been finished, elevator, FACP, balance of notification, etc. all tested okay. Final pending one SD for door release at the trash room level P1 to be tested (missing power to overhead door), and provision of resubmittal plans for field modifications including added ID detectors, hoistway devices, deleted points, accurate matrix, etc. as discussed.
INSP-Alarm Testing2/11/20092/12/20092/12/2009APART
DetailsForrest France
Discussed plan resubmittals due to modifications including 13 added SD for dampers in the common corridors, added heat and smoke detectors in the elevator hoistway, relay for the mag locks at the main lobby doors, changes in the matrix for unused CR at the elevator smoke doors. Walkthrough for the basement level parking garage completed-noted one overspaced area at a handicap accessible parking space. Discussed project inspection schedule, also need to provide list of signals recieved during pre-testing.
FIR-Aging Inspection5/30/20085/30/20085/30/2008 DONE
DetailsForrest France
Under construction, work in progress.
Issue and Print Permit  2/28/2008  
Plan assigned to (Mike)2/6/2008 2/25/2008 PASS
DetailsKenneth R Roule
See review notes for comments.
PLANS/APPL TAKEN TO FRONT DESK  2/25/2008  
Inspection Record Card- Fire2/25/2008 2/25/2008 DONE
DetailsPatricia Smith
Telephone call  2/25/2008 DONE
t/c w robert gobler at ###-#### - permit ready and fees given
Permit Ready to Issue  2/25/2008 DONE
Case Summary  2/6/2008  
Application received  2/6/2008