Miscellaneous action | | | 5/8/2009 | | DONE |
|
|
|
plans taken to records for scanning
|
INSP-Final Inspection | 7/2/2008 | 7/2/2008 | 7/2/2008 | A | PASS |
Forrest France
|
|
|
Fire alarm permit work passed field testing including new nac panel, duct smokes, initiation and notification appliances, minor field modifications accepted, incorrect descriptor at one duct detector FCU 3 amended while on site, signal report okay, fire alarm permit finaled.
|
FIR-Aging Inspection | 5/21/2008 | 5/21/2008 | 5/21/2008 | | DONE |
Forrest France
|
|
|
Under construction, work in progress.
|
Issue and Print Permit | | | 2/20/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/19/2008 | | 2/19/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 2/19/2008 | | DONE |
|
|
|
t/c w charlie bayne at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 2/19/2008 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 2/18/2008 | | 2/18/2008 | | DONE |
Sam Rogers
|
|
|
|
Alarm Plan Check | | | 2/18/2008 | | PASS |
|
|
|
Plans approved subject to RED annotations and plan review comments. Phoned Charlie Bayne (Designer) and discussed comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/18/2008 | | DONE |
|
|
|
|
Plan assigned to (Mike) | 2/6/2008 | | 2/11/2008 | | PASS |
Cathy Brown
|
|
|
2/11/2008 09:28:25 CMB - activity updated through activity FIRA22 from case FIR08-00068.
|
Application received | | | 2/6/2008 | | |
|
|
|
|