Permit Information
Permit NumberFIR08-00112
StatusFinaled
Name ROMAR ELECTRIC
Site Address 1111 W JEFFERSON ST
Project NameBOISE - 1111 W JEFFERSON
Customer Number 
ePlanReview 
Description
This permit is to upgrade the fire alarm system on the fourth floor for a tenant improvement ( Existing ).BLD07-03251
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/4/2008 DONE
Plans taken to records to scan
INSP-Final Inspection3/28/20083/28/20083/28/2008APASS
DetailsForrest France
Corrections verified for compliance, mag lock relay programming for three access control doors repaired while on site, permit finaled.
INSP-Final Inspection3/25/20083/26/20083/26/2008PFAIL
DetailsForrest France
Noted four overspaced notification devices, two smoke detectors will need relocated, transponder panel has been moved from location shown on plans, battery trouble at the transponder is incorrectly descripted, speaker at one appliance at the cafeteria seating area is not operating correctly, noted cd ratings at various strobes are different from plan set, remainder of notification and initiation devices on the 4th floor tested acceptable, also tested kitchen hood alarm interconnection and freight elevator smoke guard door.
Issue and Print Permit  2/27/2008 DONE
Plan assigned to (SAM)2/26/2008 2/26/2008 PASS
DetailsKenneth R Roule
See attached comments on fire plan review notes.
PLANS/APPL TAKEN TO FRONT DESK  2/26/2008  
Inspection Record Card- Fire2/26/2008 2/26/2008 DONE
DetailsPatricia Smith
Telephone call  2/26/2008 DONE
t/c w cathy at romar elec. ###-#### - permit ready and fees given
Permit Ready to Issue  2/26/2008 DONE
Plan assigned to (Mike)2/7/2008 2/8/2008 PASS
DetailsCathy Brown
2/8/2008 10:02:12 CMB - activity updated through activity FIRA22 from case FIR08-00051.
Application received  2/7/2008