Miscellaneous action | | | 6/4/2008 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 5/2/2008 | 5/5/2008 | 5/5/2008 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 5/1/2008 | 5/2/2008 | 5/2/2008 | A | FAIL |
Troy Cobbley
|
|
|
I was at this project twice today. The first time I found that there was only one phone line being used. I ended the inspection there. I came back after Art, the technician, provided a second phone line. All items have been tested but some corrections are required. A map needs to be available at the facp, the old facp and devices need demoed, the phone lines need rerouted, the low air signals need to report as supervisory and not troubles and the PIV needs to signal the facp after 2 1/2 turns and not report as an alarm but as a supervisory signal. The horns are not syncronized either.
|
Issue and Print Permit | | | 4/11/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/3/2008 | | 4/3/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 4/3/2008 | | DONE |
|
|
|
t/c w dave whiting at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 4/3/2008 | | DONE |
|
|
|
|
Alarm Plan Check | | | 4/2/2008 | | PASS |
|
|
|
Alarm plans are approved per attached comments. A fire pump will not be installed and is not required per latest comments under the Sprinkler permit.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/2/2008 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 3/14/2008 | | 3/31/2008 | | PASS |
Sam Rogers
|
|
|
3/31/2008 13:36:25 SLR - activity updated through activity FIRA22 from case FIR07-00929.
|
Alarm Plan Check | 3/21/2008 | | 3/21/2008 | | PEND |
Sam Rogers
|
|
|
Per the fire alarm plans, there is no fire pump or pump room. I called Randy at DeBest (###-####) and learned that the design for the sprinkler FIR07-00929 permit is based on eliminating the fire pump (which was shown on FIR07-00374) at the request of the owner who told them he would eliminate rack storage and go to solid piled storage. I requested that we visit the site to verify that the owner intends to do that and if he has eliminated the racks yet. We do not want to approve the design/installation of a sprinkler design designed for solid piled storage unless they are definitely willing to eliminate the existing rack storage. He will set up an appointment for us to visit. Meantime, we are holding off on the approval of the fire alarm permit FIR08-00122.
|
Plan resubmittals received | | | 3/14/2008 | | |
|
|
|
received three copies of application, submittal binder and sheet F2 of 2; taken to Fire Review
|
Plan assigned to (Mike) | 2/14/2008 | | 2/26/2008 | | PASS |
Michael Timmerman
|
|
|
2/26/2008 10:59:18 MWT - activity updated through activity FIRA22 from case FIR08-00122.
|
Alarm Plan Check | | | 2/26/2008 | | FAIL |
Troy Cobbley
|
|
|
Plans are being denied. Based on telcon with dave whiting there is an existing smoke detection system in the warehouse this is intended to be demo'd; shall be shown on the plans and permit. See other annotations on the returned drawings for additional items to be addressed on the resubmittals.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/26/2008 | | DONE |
Troy Cobbley
|
|
|
Plans taken to front desk for contractor pickup. No written comments. However the plans have been annotated with items needing addressed.
|
Plan assigned to (SAM) | 2/26/2008 | | 2/26/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 2/26/2008 | | DONE |
|
|
|
left vm for dave whiting at ###-#### - permit needs to be picked up and resubmitted
|
Permit Ready to Issue | | | 2/26/2008 | | DONE |
|
|
|
|
Application received | | | 2/14/2008 | | |
|
|
|
|