Permit Information
Permit NumberFIR08-00124
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 4719 S MARKET ST
Project Namephase 1
Customer Number 
ePlanReview 
Description
The data has been moved to a Word document attached to this case.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/4/20086/4/20086/4/2008PPASS
DetailsForrest France
Noted defficiencies verified for correction, fire sprinkler final inspection passed.
INSP-Final Inspection5/28/20085/29/20085/29/2008AFAIL
DetailsForrest France
Defficiencies noted include missing stock of ESFR heads at the riser head box, overspaced upright heads at the new grade level riser room, 3 branchlines at the warehouse area are too low for pendent ESFR head listing, pendent heads at the office storage room and men's restroom are obstructed by surface mounted lights, DP at the cooler condensers have been added.
INSP-Final Inspection5/27/20085/28/20085/28/2008PCANC
DetailsForrest France
Scheduled by a contractor via Hello! on 5/27/2008 at 4:28:25 PM. Contact: ###-####. Overbooked
INSP-Final Inspection5/20/20085/21/20085/21/2008ANR
DetailsForrest France
rod Phone #: ###-####
INSP-Sprinkler Rough-in/Hydro5/20/20085/21/20085/21/2008APART
DetailsForrest France
Hydrostatic test for the east office area remodel and addition passed.
INSP-Final Inspection4/1/20084/2/20084/2/2008PPART
DetailsForrest France
Installed approx 10 trim rings in the new spirit offices. No other inspection performed under this permit. KR
INSP-Sprinkler Rough-in3/13/20083/14/20083/14/2008PPART
DetailsForrest France
Sprinkler rough-in at the office area hard lid ceilings is approved for cover, noted one head to be installed under the stairway combustible concealed space, sidewinder sammy screws for hanger attatchments must be installed per manufacturers listing requirements, new DP heads at the beer cooler are acceptable as installed pending the addition of three heads where refrigeration units block coverage. NOTE: The existing ESFR upright heads at the warehouse area have been compromised by the placement of new insulation and backing at the roof deck resulting in sprinkler obstruction and violation of the head listing, permit will not be finaled until this situation is corrected.
Issue permit  3/5/2008  
PLANS/APPL TAKEN TO FRONT DESK  3/3/2008 DONE
Inspection Record Card- Fire3/3/2008 3/3/2008 DONE
DetailsCathy Brown
Permit Ready to Issue  3/3/2008 DONE
Telephone call  3/3/2008 DONE
tlk to jim danes of americna fire ###-#### that permit and fees are ready to be picked up
Sprinkler Plan Check2/14/2008 2/28/2008 PASS
Details
Plans and calculations are approved by Bryan Johnson
Application received  2/14/2008  
Case Summary  2/14/2008  
Pending Assignment by SAM2/14/2008