INSP-Final Inspection | 8/15/2008 | 8/15/2008 | 8/15/2008 | P | PASS |
Forrest France
|
|
|
Field verified noted correction items, fire sprinkler permit finaled.
|
Miscellaneous action | | | 8/14/2008 | | DONE |
|
|
|
Special approval of fireplace sprinkler spacing deficiency.
Following email sent to Shiloh 8/14/08: "Cam
We are willing to accept the minor deficiencies as stated below. When you have the other correction items completed, please reschedule a sprinkler inspection and Forrest will approve this particular spacing issue, based on verification of the measurements stated below.
Regards,
Sam Rogers
Email from Cam at Shiloh: "Thank you for your time and effort in addressing the issue with the Bonney Residence. As per our conversation, the distances of the sprinkler heads from the glass front of the fireplaces are as follows. The upstairs sprinkler head is 4'-11.25" from the glass plate, and the basement sprinkler head is 4'-10.5" from the glass plate. We used a weighted plum and measured from the center of the sprinkler head to the glass plate."
|
INSP-Final Inspection | 8/8/2008 | 8/11/2008 | 8/11/2008 | P | FAIL |
Forrest France
|
|
|
Correction items include missing test orfice at the inspectors connection, painted head at the furnace closet, missing escutcheons at two closets, pendent heads at both the upstairs and basement level fireplaces must meet distance requirements per NFPA 13D table 7.5.5.3-also noted on plan set, will test the outside bell at next inspection.
|
INSP-Final Inspection | 8/7/2008 | 8/8/2008 | 8/8/2008 | P | DEFR |
Forrest France
|
|
|
Rescheduled for Monday, 8/11.
|
INSP-Supply line flush | 5/1/2008 | 5/2/2008 | 5/2/2008 | P | PART |
Forrest France
|
|
|
UG fire supply line flush completed satisfactory.
|
INSP-Sprinkler Rough-in | 4/30/2008 | 4/30/2008 | 4/30/2008 | P | PART |
Forrest France
|
|
|
Re-inspection for noted defficient items, overhead rough-in install is okay for cover.
|
INSP-Sprinkler Rough-in | 4/28/2008 | 4/29/2008 | 4/29/2008 | A | PART |
Forrest France
|
|
|
Approved overhead rough-in at all areas except as noted in two locations including a missed head and one branch line arm-over to be re-routed due to excessive pipe deflection radius. Cold cavity tenting appears satisfactory.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/19/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 3/19/2008 | | 3/19/2008 | | DONE |
Cathy Brown
|
|
|
|
Telephone call | | | 3/19/2008 | | DONE |
|
|
|
tlk to lilly at ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 3/19/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 3/19/2008 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/3/2008 | | 3/14/2008 | | PASS |
|
|
|
Plans & Calculations are approved by Bryan Johnson
|
Plan resubmittals received | | | 3/3/2008 | | |
|
|
|
received "5" application with books & plans- put plans on fire shelf
|
Sprinkler Plan Check | 2/19/2008 | | 2/27/2008 | | FAIL |
|
|
|
These plans were denied due to flawed calculations. Upon request, the denied set may be retrieved from my office for salvage. The denied set will be maintained for 5 working days.
Bryan Johnson
|
Application received | | | 2/19/2008 | | |
|
|
|
|
Pending Assignment by SAM | 2/19/2008 | | | | |
|
|
|
|