Permit Information
Permit NumberFIR08-00143
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 350 N MILWAUKEE ST
Project NameBTSM
Customer Number 
ePlanReview 
Description
SimplexGrinnell is adding two smoke detectors, two heat detectors and elevator recall functions to an existing elevator.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/4/2012 DONE
Plans taken to records for scanning.
INSP-Final Inspection3/8/20123/12/20123/12/2012APASS
DetailsTroy Cobbley
Permit finaled
FIR-Aging Inspection1/18/20121/18/20121/23/2012 NR
DetailsTroy Cobbley
I met with Tamara and Charlie and discussed the project status. The projects will be followed up on and their status relayed to me.
FIR-Aging Inspection9/12/20119/12/20119/15/2011 NR
DetailsTroy Cobbley
I splok with Ernie, mall managment, and Joe with Lightining Electric, about getting this project inspected and finaled.
INSP-Conference5/13/20115/13/20115/13/2011PDONE
DetailsTroy Cobbley
I spoke to Phil with Schindler elevator about the job status. He stated that the firemans hat was now functional and that Brian with Lighting Electric would be scheduling the inspection.
FIR-Aging Inspection4/27/20114/27/20115/5/2011 NR
DetailsTroy Cobbley
I spoke to Tammy with SimplexGrinnell about getting work completed and the inspection finaled. She is following up and will contact me with the project status.
FIR-Aging Inspection2/25/20112/25/20113/1/2011 NR
DetailsTroy Cobbley
I spoke to Brian with Lightning Electric about the job status
INSP-Alarm Testing12/6/201012/6/201012/6/2010PFAIL
DetailsTroy Cobbley
Provide city approved drawings and a flashing hat in the elevator car when the shaft and machine room detector is activated.
FIR-Aging Inspection11/23/201011/23/201011/24/2010 NR
DetailsTroy Cobbley
I spoke to Brian with Lighting Electric, who was with Ernie, and they were going to address this permit. I also spoke to Charlie with SimplexGrinnell.
INSP-Final Inspection4/23/20104/26/20104/26/2010ACANC
DetailsTroy Cobbley
Inspection Canceled. Per the contractor, the elevator contractor was unavailable.
Telephone call  4/19/2010 DONE
Spoke to Charlie, he indicated this permit would be called in this week.
INSP-Final Inspection6/9/20096/11/20096/11/2009PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 6/9/2009 at 7:54:26 AM. Contact: ###-####.
INSP-Final Inspection6/9/20096/9/20096/9/2009PFAIL
DetailsTroy Cobbley
The elevator contractor could not find a reset key at first. After the key was found the beam detector in the main corridor was tested. The elevator recalled to the second floor but would not reset. The elevator contractor was trying to trouble shoot the problem when I left.
Telephone call  5/8/2009 DONE
spoke to Charlie Bayne who stated work is still in progress
FIR-Aging Inspection5/27/20085/27/20085/28/2008 NR
DetailsTroy Cobbley
wip
Issue and Print Permit  2/26/2008 DONE
Plan assigned to (Mike)2/21/2008 2/25/2008 PASS
DetailsMichael Timmerman
2/25/2008 09:33:38 MWT - activity updated through activity FIRA22 from case FIR08-00143.
Alarm Plan Check2/25/2008 2/25/2008 DONE
DetailsTroy Cobbley
This was a quick permit. The operation of the fireman's hat upon lobby smoke detector activation was unclear. I spoke to Charlie about this and notes have been made on the drawings stating compliance is required with the elevator code. This will be field verified by the fire inspector. There are no separate written comments.
PLANS/APPL TAKEN TO FRONT DESK  2/25/2008 DONE
DetailsTroy Cobbley
Inspection Record Card- Fire2/25/2008 2/25/2008 DONE
DetailsPatricia Smith
Telephone call  2/25/2008 DONE
left vm for charlie bayne at ###-#### - permit ready and fees given
Permit Ready to Issue  2/25/2008 DONE
Application received  2/21/2008