Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR08-00168
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 2604 W STATE ST
Project NameST MARY'S CATHOLIC CHURCH ADD.
Customer Number 
ePlanReview 
Description
St. Mary's Catholic Church Addition and Remodel - To remodel an existing 4,250 square foot, existing church building and construct a 9,750 square foot church addition on the west end of the existing church building. The addition will have a large nave, a narthex, cry room, sacristy, equipment rooms and two restrooms. The new addition is constructed of masonry and steel stud exterior walls and steel structural frame roof system. The existing church is constructed of masonry exterior walls and wood framing. This permit also includes related site improvements. This building is fully fire sprinkled. The sprinklers are used for area increase. All construction per the approved plans and attached comment list. The scope of work for the fire alarm is to install a new manual fire alarm system in the remodel/addition.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/8/2009 DONE
plans taken to records for scanning
INSP-Final Inspection12/18/200812/18/200812/18/2008PPASS
DetailsForrest France
Balance of fire alarm permit work passed site inspection, permit finaled.
INSP-Final Inspection12/16/200812/17/200812/16/2008ACANC
DetailsForrest France
mike Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
INSP-Alarm Testing8/28/20088/28/20088/28/2008PNR
DetailsForrest France
Phase two building construction is not yet complete.
INSP-Alarm Testing5/28/20085/29/20085/29/2008PPART
DetailsForrest France
Listed correction notice items verified for compliance, permit final pending completion of phase two remodel work at the east side including notification appliances and riser #2 alarm and supervisory conditions.
INSP-Final Inspection5/23/20085/27/20085/27/2008AFAIL
DetailsForrest France
Provide as-built plans indicating field change in notification circut wire guage from 14 to 18, the deletion of a duct smoke detector at the electrical room and the additon of a requried notification appliance at the basement storage room per review notes, provide an updated map at the panel, the door to the FACP room needs signage, sprinkler system riser #2 is not in service to complete testing, annotated areas not finished at this time including phase 2 appliance circut, central station account information is not correct regarding type and description of signals recieved-will need to retest.
INSP-Final Inspection5/22/20085/23/20085/23/2008ACANC
DetailsForrest France
mike Phone #: ###-#### Overbooked, inspection rescheduled as agreed with sub and general contractors.
Issue and Print Permit  3/7/2008 DONE
Plan assigned to (Mike)3/3/2008 3/5/2008 PASS
DetailsMichael Timmerman
3/5/2008 10:27:44 MWT - activity updated through activity FIRA22 from case FIR08-00168.
Alarm Plan Check3/5/2008 3/5/2008 PASS
DetailsTroy Cobbley
Plans approved on the first review with written comments.
PLANS/APPL TAKEN TO FRONT DESK  3/5/2008 DONE
Telephone call  3/5/2008 DONE
t/c w mike at ###-#### - permit ready and fees given
Inspection Record Card- Fire3/5/2008 3/5/2008 DONE
DetailsPatricia Smith
Permit Ready to Issue  3/5/2008 DONE
Application received  3/3/2008