INSP-Final Inspection | 7/30/2008 | 7/30/2008 | 7/30/2008 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled, repairs are complete.
|
INSP-Final Inspection | 7/25/2008 | 7/25/2008 | 7/25/2008 | P | FAIL |
Forrest France
|
|
|
Missing a pressure reducing valve at the riser due to gridded overhead system design, one pendent head at the main entry vestibule is obstructed by an adjacent surface mounted light fixture.
|
INSP-Sprinkler Rough-in | 6/24/2008 | 6/25/2008 | 6/25/2008 | A | FAIL |
Forrest France
|
|
|
See stamped plan set for locations in need of adjustment including two overspaced pendent heads at the nurse station and three SSU's above the X-ray room which exceed min. spacing, also notified contractor to call in the shell FIR permit for rough-in inspection at next scheduled visit.
|
Issue and Print Permit | | | 5/6/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/9/2008 | | 4/9/2008 | | DONE |
Patricia Smith
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/9/2008 | | DONE |
|
|
|
|
Telephone call | | | 4/9/2008 | | DONE |
|
|
|
left message w aleshia for gerald ebling at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 4/9/2008 | | DONE |
|
|
|
|
Sprinkler Plan Check | 3/18/2008 | | 4/8/2008 | | PASS |
|
|
|
plans are approved
|
Application received | | | 3/18/2008 | | |
|
|
|
|
Pending Assignment by SAM | 3/18/2008 | | | | |
|
|
|
|