Miscellaneous action | | | 5/8/2009 | | DONE |
|
|
|
plans taken to records for scanning
|
INSP-Final Inspection | 4/23/2009 | 4/24/2009 | 4/24/2009 | A | PASS |
Forrest France
|
|
|
Monitor module for alarm condition tie-in at the existing parking garage panel tested okay per condition of agreement letter, smoke alarm retested okay at unit 901, new plan sheets with field modifications verified for changes at the basement and 1st floors, portions of fire alarm work not completed per the scope of this permit yet shown on stamped drawings are to be done under FIR08-00754 (existing parking structure notification devices, FS and FP monitoring, FJ, and east and west elevator control functions), NFPA 72 completion report recieved. NOTE: Contractor to provide revised 18th floor plan for field device location changes, faxed copy of supervising station signals report, NFPA 72 record of inspection and testing per review note #4, and current map at the panel when FIR08-00754 work is finished.
|
INSP-Alarm Testing | 4/23/2009 | 4/23/2009 | 4/23/2009 | A | PART |
Forrest France
|
|
|
Testing completed for the remainder of the new elevator control devices including heat detectors at 3rd and 4th floors and elevator machine room, (damaged heat detector at the 4th floor replaced while on site), shunt trip and voltage monitoring, retested non-functional smoke detector at the 5th floor elevator lobby (replaced while on site), 9th floor flow switch retested, 5th 6th and 7th floor in duct detectors for fire smoke dampers, tested all smoke alarms at residential units on the 8th and 9th floors. NOTE: Need to provide sprinkler monitoring for the exisitng system at the adjacent parking structure per TOC agreement letter item #6/7, non-functional smoke alarm at unit 904, plans need to show accurate locations of devices at the basement, 1st and 18th floors (flow switch, tamper valves, SD and HD), post map at the fire command center, approved plans to reflect scope of work completed-new devices and interconnection to to systems at the adjacent building are not installed at this time, provide record of completion and inspection and testing reports.
|
INSP-Alarm Testing | 4/20/2009 | 4/22/2009 | 4/22/2009 | P | PART |
Forrest France
|
|
|
Completed smoke alarm testing for all units at floors 5,6,and 7, primary and alternate floor recall for the new elevator including fire hat functions tested okay, 4th floor fire alarm testing passed. NOTE: Missing equipment to test the heat detectors at the 3rd, 4th and elevator machine room, shunt trip and voltage monitoring also needs tested, smoke detector at the 5th floor elevator lobby failed to operate, plans indicate heat and smoke detection in the hoistway which is not installed-devices are located in the machine room, need to locate duct detectors for testing at the 5th, 6th and 7th floors, flow switch at the 9th floor needs repair/retest.
|
INSP-Alarm Testing | 4/20/2009 | 4/21/2009 | 4/21/2009 | P | PART |
Forrest France
|
|
|
Contact Rafe. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong
|
INSP-Alarm Testing | 4/20/2009 | 4/20/2009 | 4/20/2009 | P | DONE |
Troy Cobbley
|
|
|
The items inspected today were the firemans phones. The phone operated except the 15th floor east which would cut out and needs replaced. Also phone jacks are shown to be installed on the exterior stairways but have not been installed.
|
INSP-Final Inspection | 4/13/2009 | 4/17/2009 | 4/17/2009 | P | PART |
Forrest France
|
|
|
Items tested today include the remainder of manual pull stations on floors 18 thru the basement with the exception of one MP at the 1st floor west side tenant space and two MP at the 18th floor, no access to test the 4th level parking garage due to floor coating, audibility retest at the common corridors and condo units completed satisfactory, tampers at the floor control valves 5th -18th post relocation tested okay, 14th floor corridor speaker strobe repaired, new strobe at the fire command center tested ok, need access to the communication panel for fire phone testing, 11th floor speakers at units are not ready for testing due to construction underway. Need to post an accurate building map at the panel, provide new plan sheets for the basement and 1st floor device location changes for tamper and flow switches..
|
INSP-Final Inspection | 4/13/2009 | 4/16/2009 | 4/17/2009 | P | PART |
Forrest France
|
|
|
Tested notification devices for the 18th thru basement levels via one manual pull station per level, noted one non-functional speaker strobe on the 14th floor corridor, need to verify MP's at the 18th floor balcony are wp, noted audibility measurements at several condos and common corridors on the 5th thru 11th levels is not sufficient, replaced av's in the basement corridor tested okay, provide strobe notification at the fire command center as discussed. Inspection completed 4/16..
|
INSP-Final Inspection | 4/13/2009 | 4/15/2009 | 4/17/2009 | P | PART |
Forrest France
|
|
|
Completed walkthrough for the remainder of floors 18th thru 5th with the exception of residential units for smoke alarm locations. Noted one missing speaker/strobe at the 15th floor corridor, need to adjust cd setting at one strobe 18th floor balcony. Noted areas on plans not finished at this time including points at the existing adjacent parking structure including the east and west elevators, notification, and sprinkler system monitoring. Inspection completed 4/15..
|
INSP-Final Inspection | 4/13/2009 | 4/14/2009 | 4/17/2009 | P | PART |
Forrest France
|
|
|
On site meeting regarding heights at audible notification devices in the residential units, listing for wall mounted appliances that appear to be ceiling type, item #6 regarding sprinkler system monitoring interface for the existing building per temporary occupancy agreement letter, field modifications, project phasing for completion of work indicated per approved fire alarm plans, and locations for smoke alarms to be in compliance with NFPA 72 chaper 11. Completed testing for fire sprinkler floor control manifolds at floors 5 thru 18, noted 9th and 16th floor flow switches failed to operate, need to relocate control valves. Inspection completed 4/14..
|
INSP-Final Inspection | 4/13/2009 | 4/13/2009 | 4/17/2009 | P | FAIL |
Forrest France
|
|
|
Walkthrough completed for the basement, 1st, 2nd and 3rd floors. Noted plans indicate 18 ah batteries( 7ah are installed) , plans show a nac and one sd in the basement electrical room which are not installed, notification devices at the basement corridor are wall mount type positioned on the ceiling, scope of work per approved plan is not finished for interconnection to the exitsing adjacent builidng alarm devices, noted smoke alarms and audible notification at numerous residential units are incorrectly located per NFPA 72 guidelines, missing lockouts at breakers to the FACP. NOTE: Phone lines, power loss, battery trouble, smoke above panel tested okay. Fire pump and all sprinkler system monitoring points for the basement, 1st and 2nd floors completed okay-need to show accurate locations of basement backflow valves and flow switch and ISO vavles for the standpipe on plans and map. Inspection completed 4/13..
|
Plan assigned to (Stephanie) | 4/7/2009 | | 4/10/2009 | | DONE |
Stephanie L. Cobbley
|
|
|
4/10/2009 08:59:10 SLC - activity updated through activity FIRA24 from case FIR08-00234.
|
Alarm Plan Check | 4/10/2009 | | 4/10/2009 | | PASS |
Stephanie L. Cobbley
|
|
|
see review comments
|
PLANS TAKEN FRONT DESK ALARM | | | 4/10/2009 | | DONE |
|
|
|
Approved plans available at front counter
|
Inspection Record Card- Fire | 4/10/2009 | | 4/10/2009 | | DONE |
|
|
|
|
Telephone call | | | 4/10/2009 | | DONE |
|
|
|
t/c w phil bassick at ###-#### - permit ready (plan mod) and fees given
|
Permit Ready to Issue | | | 4/10/2009 | | DONE |
|
|
|
|
(F) Reprint permit | | | 4/10/2009 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 4/10/2009 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/7/2009 | | |
Stephanie L. Cobbley
|
|
|
Plan Modification: Received two copies of application and sheets FA0.0, FA2.00, FA2.01, FA2.02, FA2.03, FA2.04, FA2.05, FA2.06, FA2.07, FA2.08, FA2.09, FA2.10, FA2.11, FA2.12, FA2.14, FA2.15, FA2.16, FA2.17, FA2.18, FA-3.0, FA-3.1; taken to Fire Review.
|
(F) Reprint permit | | | 9/5/2008 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 9/5/2008 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/2/2008 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/2/2008 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 9/2/2008 | | |
|
|
|
|
Inspection Record Card- Fire | 9/2/2008 | | 9/2/2008 | | DONE |
|
|
|
|
Telephone call | | | 9/2/2008 | | DONE |
|
|
|
t/c w phil bassick at ###-#### - permit ready and no fees
|
Override - Parcel Holds | | | 9/2/2008 | | |
|
|
|
|
Permit Ready to Issue | | | 9/2/2008 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 8/29/2008 | | |
|
|
|
|
Inspection Record Card- Fire | 8/29/2008 | | 8/29/2008 | | DONE |
|
|
|
|
Telephone call | | | 8/29/2008 | | DONE |
|
|
|
left vm for phil bassick at ###-#### - permit ready and fees given
|
Override - Parcel Holds | | | 8/29/2008 | | |
|
|
|
|
Permit Ready to Issue | | | 8/29/2008 | | DONE |
|
|
|
|
(F) Reprint permit | | | 8/29/2008 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 8/29/2008 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 8/28/2008 | | 8/28/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
per stephanie c.
|
Alarm Plan Check | | | 8/28/2008 | | PASS |
|
|
|
see redlines and review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/28/2008 | | DONE |
|
|
|
|
FIR-Aging Inspection | 8/26/2008 | 8/26/2008 | 8/26/2008 | | DONE |
Forrest France
|
|
|
Work in progress, building under construction.
|
Override - Parcel Holds | | | 5/22/2008 | | |
|
|
|
|
Issue and Print Permit | | | 5/22/2008 | | DONE |
|
|
|
|
(F) Reprint permit | | | 4/14/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/14/2008 | | 4/14/2008 | | DONE |
Patricia Smith
|
|
|
|
Permit Ready to Issue | | | 4/14/2008 | | DONE |
|
|
|
|
Plan assigned to (Ken) | 4/11/2008 | | 4/11/2008 | | PASS |
Kenneth R Roule
|
|
|
See fire alarm review notes.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/11/2008 | | |
|
|
|
|
Application received | | | 4/1/2008 | | |
|
|
|
|