Case Summary | | | 12/9/2008 | | |
|
|
|
|
Miscellaneous action | | | 6/4/2008 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 4/25/2008 | 4/28/2008 | 4/28/2008 | A | PASS |
Forrest France
|
|
|
Noted correction at the previous inspection verified for completion, new fire alarm work passed field testing, permit finaled.
|
INSP-Final Inspection | 4/24/2008 | 4/25/2008 | 4/25/2008 | A | FAIL |
Forrest France
|
|
|
The smoke detector at the kitchen side of the doors is not in compliance with NFPA 72 5.7.4.1 regarding proximity to the HVAC register.
|
Issue and Print Permit | | | 4/9/2008 | | DONE |
|
|
|
|
Pending Assignment by SAM | 4/2/2008 | | 4/8/2008 | | PASS |
Kenneth R Roule
|
|
|
field verify.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/8/2008 | | |
|
|
|
|
Inspection Record Card- Fire | 4/8/2008 | | 4/8/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 4/8/2008 | | DONE |
|
|
|
left message w craig for jason minnick at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 4/8/2008 | | DONE |
|
|
|
|
Application received | | | 4/2/2008 | | |
|
|
|
|