INSP-Final Inspection | 9/8/2008 | 9/9/2008 | 9/9/2008 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 9/5/2008 | 9/5/2008 | 9/5/2008 | P | FAIL |
Troy Cobbley
|
|
|
Provide expansion tank for the anti-freeze loop, provide certification for the backflow, provide inspection tag and provide electric alarm bell.
|
INSP-Sprinkler Rough-in/Hydro | 7/9/2008 | 7/9/2008 | 7/9/2008 | A | PASS |
Troy Cobbley
|
|
|
Overhead hydro test passed. Rough-in passed.
|
INSP-Sprinkler Rough-in/Hydro | 7/8/2008 | 7/8/2008 | 7/8/2008 | P | FAIL |
Troy Cobbley
|
|
|
The overhead hydro failed. No rough-in inspection performed.
|
Issue permit | | | 5/9/2008 | | |
|
|
|
|
Inspection Record Card- Fire | 5/8/2008 | | 5/8/2008 | | DONE |
Patricia Smith
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/8/2008 | | DONE |
|
|
|
|
Telephone call | | | 5/8/2008 | | DONE |
|
|
|
t/c w don curtis at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 5/8/2008 | | DONE |
|
|
|
|
Sprinkler Plan Check | 4/2/2008 | | 5/7/2008 | | PASS |
|
|
|
plans are approved
|
Case Summary | | | 4/24/2008 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/24/2008 | | |
|
|
|
received application and three copies of submittal packet and six copies of sheets FP1, FP2; taken to fire review
|
Sprinkler Plan Check | 4/2/2008 | | 4/21/2008 | | FAIL |
|
|
|
These plans were denied for lack of or incorrect information. Upon request, the rejected set of plans and data may be retrieved from my office for salvage. The rejected set will be maintained for 5 working days.
|
Case Summary | | | 4/2/2008 | | DONE |
|
|
|
|
Application received | | | 4/2/2008 | | |
|
|
|
|
Pending Assignment by SAM | 4/2/2008 | | | | |
|
|
|
|