Miscellaneous action | | | 5/8/2009 | | DONE |
|
|
|
plans taken to records for scanning
|
INSP-Final Inspection | 11/17/2008 | 11/18/2008 | 11/18/2008 | P | PASS |
Forrest France
|
|
|
AM fire alarm notification appliance testing completed acceptable, field modifications noted on as-built plans okayed, corrections per last inspection repaired, permit finaled. NOTE: mag locks at access control doors did not appear to drop out on fire alarm condition per IFC requirements-not included in the scope of this permit work.
|
INSP-Final Inspection | 6/16/2008 | 6/17/2008 | 6/17/2008 | A | FAIL |
Troy Cobbley
|
|
|
The first audio/visual I looked at has not been set at the correct candella. Also when we activated the audio/visual devices the audio was not in sync or even in temporal. The visuals started flashing at different rates or not at all. Brian said it appears that the NAC panel has failed. Testing was stopped.
|
Alarm Plan Check | 4/29/2008 | | 4/29/2008 | | PASS |
Stephanie L. Cobbley
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/29/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/29/2008 | | 4/29/2008 | | DONE |
Cathy Brown
|
|
|
|
Telephone call | | | 4/29/2008 | | |
|
|
|
tlk to charlie bayne ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 4/29/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/29/2008 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/25/2008 | | |
|
|
|
received application and two folders with plan sheets 1, 2, 3; taken to fire review
|
Plan assigned to (Stephanie) | 4/22/2008 | | 4/22/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | | | 4/22/2008 | | FAIL |
|
|
|
Plan review comments faxed to designer; annotated plans available for pickup at front counter if desired. One set retained for reference.
|
Application received | | | 4/11/2008 | | |
|
|
|
|
Case Summary | | | 4/11/2008 | | |
|
|
|
|
Pending Assignment by SAM | 4/11/2008 | | | | |
|
|
|
|