Permit NumberFIR08-00265
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 6074 N DISCOVERY PL
Project NameMARVELL COLUMBIA BUILDING
Customer Number 
ePlanReview 
Description
This fire alarm permit is to voluntarily upgrade the existing sprinkler monitoring system to include full A/V notification in accordance with current code requirements.

There is no building permit associated with this project.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/8/2009 DONE
plans taken to records for scanning
INSP-Final Inspection11/17/200811/18/200811/18/2008PPASS
DetailsForrest France
AM fire alarm notification appliance testing completed acceptable, field modifications noted on as-built plans okayed, corrections per last inspection repaired, permit finaled. NOTE: mag locks at access control doors did not appear to drop out on fire alarm condition per IFC requirements-not included in the scope of this permit work.
INSP-Final Inspection6/16/20086/17/20086/17/2008AFAIL
DetailsTroy Cobbley
The first audio/visual I looked at has not been set at the correct candella. Also when we activated the audio/visual devices the audio was not in sync or even in temporal. The visuals started flashing at different rates or not at all. Brian said it appears that the NAC panel has failed. Testing was stopped.
Alarm Plan Check4/29/2008 4/29/2008 PASS
DetailsStephanie L. Cobbley
PLANS/APPL TAKEN TO FRONT DESK  4/29/2008 DONE
Inspection Record Card- Fire4/29/2008 4/29/2008 DONE
DetailsCathy Brown
Telephone call  4/29/2008  
tlk to charlie bayne ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  4/29/2008 DONE
Issue and Print Permit  4/29/2008 DONE
Plan resubmittals received  4/25/2008  
received application and two folders with plan sheets 1, 2, 3; taken to fire review
Plan assigned to (Stephanie)4/22/2008 4/22/2008 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check  4/22/2008 FAIL
Plan review comments faxed to designer; annotated plans available for pickup at front counter if desired. One set retained for reference.
Application received  4/11/2008  
Case Summary  4/11/2008  
Pending Assignment by SAM4/11/2008