Miscellaneous action | | | 5/8/2009 | | DONE |
|
|
|
plans taken to records for scanning
|
INSP-Final Inspection | 10/8/2008 | 10/8/2008 | 10/8/2008 | A | PASS |
Troy Cobbley
|
|
|
fire alarm testing passed previous inpection by Troy Cobbley. KR.
|
INSP-Alarm Testing | 9/19/2008 | 9/19/2008 | 9/19/2008 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 9/11/2008 | 9/17/2008 | 9/17/2008 | P | FAIL |
Troy Cobbley
|
|
|
Everything tested ok except the strobe in the mens restroom did not function, the sample tubes in the duct smoke detectors are not in the correct holes and the exhaust tubes need to be shortened per the installation guide. Also the strobes do not stop flashing when the horns are silenced as required per NFPA 72.
|
FIR-Aging Inspection | 7/31/2008 | 7/31/2008 | 8/1/2008 | | NR |
Troy Cobbley
|
|
|
Work is in progress
|
Alarm Plan Check | 4/22/2008 | | 4/22/2008 | | PASS |
Stephanie L. Cobbley
|
|
|
Approved subject to comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/22/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 4/22/2008 | | 4/22/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 4/22/2008 | | DONE |
|
|
|
t/c w charlie bayne at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 4/22/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 4/22/2008 | | DONE |
|
|
|
|
Application received | | | 4/11/2008 | | |
|
|
|
|
Case Summary | | | 4/11/2008 | | |
|
|
|
|
Pending Assignment by SAM | 4/11/2008 | | | | |
|
|
|
|