Permit Information
Permit NumberFIR08-00287
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 1301 N ORCHARD ST
Project NameCENTER POINTE ONE / orchard pl
Customer Number 
ePlanReview 
Description
This permit is to install a new NAC panel, new A/V devices and three new duct detectors in a remodel and addition.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  7/17/2009 DONE
Taken to records for scanning.
INSP-Final Inspection7/7/20097/8/20097/8/2009PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection6/29/20096/30/20096/30/2009AFAIL
DetailsTroy Cobbley
The devices at the new riser at the east side of the building functioned correctly. The new devices in the elevator did not function correctly. An inspection will need to be resceduled with the elevator contractor.
Alarm Plan Check3/9/2009 3/16/2009 PASS
DetailsForrest France
Approved per red line plan annotations. No written comments.
PLANS/APPL TAKEN TO FRONT DESK  3/16/2009 DONE
Telephone call  3/16/2009 DONE
Details
left vm for robert gobler at ###-#### - permit ready to be picked (resubmittal)
Permit Ready to Issue  3/16/2009 DONE
Details
Inspection Record Card- Fire3/16/2009 3/16/2009 DONE
Details
CHANGE STATUS TO (ISS)  3/16/2009 DONE
(F) Reprint permit  3/16/2009 DONE
Plan resubmittals received  3/9/2009  
DetailsSam Rogers
Received application and three copies of submittal folder and pages F0.0, F1.0, F1.1, F2.0; taken to Fire Review
INSP-Alarm Testing3/2/20093/3/20093/3/2009PPASS
DetailsTroy Cobbley
The fire alarm for the Corrections area is now complete.
INSP-Alarm Testing2/26/20092/26/20092/27/2009PFAIL
DetailsTroy Cobbley
This inspection was for the Corrections tenant expansion into the new area of the first floor. NAC circuit #4 did not meet the minimum 21.6 volt requirement at the end of line. Caps were missing from the end of the sample tubes for the two duct smoke detectors tested. There have been significant changes to the notification circuits and resubmittals will be required prior to a final inspection and sign off.
FIR-Aging Inspection8/4/20088/4/20088/4/2008 NR
DetailsTroy Cobbley
work is in progress
Plan assigned to (Stephanie)4/22/2008 4/25/2008 DONE
DetailsKenneth R Roule
plans were reasigned to Ken Roule.
Plan assigned to (Ken)4/25/2008 4/25/2008 PASS
DetailsKenneth R Roule
4/25/2008 11:17:38 KRR - activity updated through activity FIRA22 from case FIR08-00287.
PLANS/APPL TAKEN TO FRONT DESK  4/25/2008  
Inspection Record Card- Fire4/25/2008 4/25/2008 DONE
DetailsPatricia Smith
Telephone call  4/25/2008 DONE
t/c w robert gobler at ###-#### - permit ready and fees given
Permit Ready to Issue  4/25/2008 DONE
Issue and Print Permit  4/25/2008 DONE
Case Summary  4/22/2008 DONE
Application received  4/22/2008  
Plan assigned to (SAM)3/9/2009    
DetailsSam Rogers