Miscellaneous action | | | 6/4/2008 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 5/7/2008 | 5/9/2008 | 5/9/2008 | A | PASS |
Forrest France
|
|
|
Fire alarm field testing passed, one notification appliance re-attatched to the wall while on site, scope of permit work finaled.
|
Issue and Print Permit | | | 5/2/2008 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/1/2008 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/1/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/1/2008 | | 5/1/2008 | | DONE |
Patricia Smith
|
|
|
|
Telephone call | | | 5/1/2008 | | DONE |
|
|
|
left vm for charlie bayne at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 5/1/2008 | | DONE |
|
|
|
|
Telephone call | | | 4/30/2008 | | DONE |
|
|
|
Left a message for Charlie Bayne letting him know the battery calculations and voltage drops did not match the riser or the plans, and that he could email me a revised set of calcs/voltage drops. Recieved revised calcs/voltage drops via email from Dante Frassa and attached to the submittal set.
|
Application received | | | 4/24/2008 | | |
|
|
|
|
Plan assigned to (Stephanie) | 4/24/2008 | | 4/24/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Case Summary | | | 4/24/2008 | | DONE |
|
|
|
|