Permit NumberFIR08-00302
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 7031 N EISENMAN RD
Project Name 
Customer Number 
ePlanReview 
Description
Work Scope: Extend the existing system 3 out to serve 18 down heads in a new 2000-ft/2 cooler where Class III non encapsulated dried food will be stored on conventional wood pallets to 20’-6” maximum storage height or -3’-0” from the bottom of the sprinkler deflector. The class III will be stored on single and double row racks. No in-rack sprinklers are required.
The surrounding sprinkler system is subject to field inspection and must meet the minimal code compliance. The installation of the sprinkler heads shall meet the manufactures installation guidelines. To field verified by a Life & Safety Field inspector. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is not attached to any other permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/21/20088/22/20088/22/2008APASS
DetailsForrest France
Noted corrections are complete, plans verified, fire sprinkler permit finaled.
INSP-Final Inspection8/20/20088/21/20088/21/2008PCANC
DetailsForrest France
INSP-Sprinkler Rough-in/Hydro7/8/20087/8/20087/8/2008PFAIL
DetailsForrest France
Completed only a preliminary field inspection as contractor did not provide approved plans, review notes, inspection record/permit card on site as required per condition of the permit for verification of compliance, missing branch line hangers at several locations, need to provide sealant at all penetrations by sprinkler drops at the cooler enclosure, two DP are not yet installed, rough-in install cannot be okayed until stamped plans and associated documents are provided.
Telephone call  5/21/2008 DONE
left vm for tom easton at ###-#### - permit ready and fees given
Permit Ready to Issue  5/21/2008 DONE
Issue and Print Permit  5/21/2008 DONE
PLANS/APPL TAKEN TO FRONT DESK  5/20/2008 DONE
Inspection Record Card- Fire5/20/2008 5/20/2008 DONE
DetailsPatricia Smith
Sprinkler Plan Check4/28/2008 5/19/2008 PASS
Details
plans & calculations are approved w/conditions by Bryan Johnson
Case Summary  4/28/2008 DONE
Application received  4/28/2008  
Pending Assignment by SAM4/28/2008