Permit NumberFIR08-00303
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 1649 W SHORELINE DR Unit: 101
Project NameAGC OFFICE BLDG-1ST FLR
Customer Number 
ePlanReview 
Description
FIR Sprinkler Scope:
The Fire Sprinkler scope consists modifying the existing protection by adding, removing and relocating 81 down heads to accommodate a new wall lay out. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-03260.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/17/20087/17/20087/17/2008PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection7/16/20087/16/20087/16/2008PFAIL
DetailsTroy Cobbley
Shell permit needs finaled first. This TI permit is ok to final when that happens.
INSP-Sprinkler Rough-in5/29/20085/30/20085/30/2008APART
DetailsTroy Cobbley
This inspection was for a first floor rough-in. The sprinkler piping can not be covered yet since final locations for the pendants is not done. No t-bar has been installed yet. The rough-in for the most part is ok. Two items have been noted. They include most of the branchline hangers to the north of the 3" main have been attached to the bottom of the beams. I referenced note #50 which does not allow this. Also the sidewall head installed at the top of the elevator shaft has not been installed in the 4" to 6" window.
INSP-Sprinkler Rough-in5/23/20085/27/20085/27/2008APART
DetailsForrest France
See stamped TI plan set for rough-in areas approved for cover at the hard lid ceilings including soffits, noted head placement to be adjusted at the conference room accordian door pocket for proper coverage, ceiling at the electrical closet appears to have been deleted-if so then walls must extend to the bottom of the deck for area separation of sprinklered and non-sprinklered spaces.
Permit Ready to Issue  5/21/2008 DONE
DetailsCathy Brown
Telephone call  5/21/2008 DONE
t/c w shawn ramsey at ###-#### - permit ready and fees given
Issue and Print Permit  5/21/2008 DONE
PLANS/APPL TAKEN TO FRONT DESK  5/20/2008 DONE
DetailsCathy Brown
Inspection Record Card- Fire5/20/2008 5/20/2008 DONE
DetailsCathy Brown
Sprinkler Plan Check4/28/2008 5/16/2008 PASS
Details
Plans are approved By Bryan Johnson
Application received  4/28/2008  
Pending Assignment by SAM4/28/2008