Miscellaneous action | | | 5/8/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 7/2/2008 | 7/3/2008 | 7/3/2008 | A | PASS |
Forrest France
|
|
|
Fire alarm inspection completed. Candella in living room and family room were changed to 75cd. Inspection and completion forms were signed and will be faxed to PDS fire on 7/7/08. KR
|
INSP-Final Inspection | 7/1/2008 | 7/1/2008 | 7/1/2008 | P | FAIL |
Forrest France
|
|
|
NFPA 72 forms, letter of completion were not filled out. No testing performed on smoke detectors, contractor did not have canned smoke. sprinkler flow switch and tamper were tested. No other testing completed.KR
|
INSP-Alarm Testing | 6/27/2008 | 6/30/2008 | 6/30/2008 | P | CANC |
Forrest France
|
|
|
Talked with David and let him know that the sprinkler permit also needs to be called in for the fire alarm testing. He will call in both permits tomorrow for finals.KR
|
Issue and Print Permit | | | 5/23/2008 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/22/2008 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/22/2008 | | DONE |
|
|
|
|
Telephone call | | | 5/22/2008 | | DONE |
|
|
|
t/c w david bauerle at ###-#### - permit ready and fees given
|
Inspection Record Card- Fire | 5/22/2008 | | 5/22/2008 | | DONE |
Patricia Smith
|
|
|
|
Permit Ready to Issue | | | 5/22/2008 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/20/2008 | | |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | | | 5/2/2008 | | FAIL |
|
|
|
Quick permit failed. See comments
|
Telephone call | | | 5/2/2008 | | DONE |
|
|
|
Left a message for David Bauerle letting him know his plans have been denied (there was no fax number available) and that he would need pick up the review comments and resubmit revisions.
|
Application received | | | 4/30/2008 | | |
|
|
|
|
Plan assigned to (Stephanie) | 4/30/2008 | | 4/30/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Case Summary | | | 4/30/2008 | | DONE |
|
|
|
|