Permit Information
Permit NumberFIR08-00313
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 720 E PARK BLVD Unit: 125
Project NameMK CENTRAL PLAZA
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add new notification devices for a 1st floor tenant improvement.
Associated building permit for reference:
BLD08-00521 (ARTHUR J GALLAGHER)( MK CENTRAL PLAZA - 1ST FLR - STE #125) To remodel a 1,606 square foot office area on the 1st floor per approved plans. Work to include: [demolition of existing flooring, existing partitions, existing main egress doors, and existing interior door,]{construction of new partitions to create 2 new offices, a conference room, open office area, copy/kitchen room, a storage room, and a data closet,} installation of new lighting, repair and replace existing suspended ceiling system as needed, install new ducts and diffusers, and install interior finishes in compliance with chapter 8 of the IBC. This building is fully fire sprinkled.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  6/4/2008 DONE
Plans taken to records to scan
INSP-Final Inspection5/27/20085/28/20085/28/2008APASS
DetailsForrest France
Defficiencies regarding voice evac repaired, fire alarm permit finaled.
INSP-Alarm Testing5/20/20085/21/20085/21/2008AFAIL
DetailsForrest France
Voice evacuation communication is not sufficiently intelligible to be clearly understood-NFPA 72 2007 7.4.1.4, noted one non-required SD at the computer room has been installed per tenant request.
Issue and Print Permit  5/19/2008 DONE
Alarm Plan Check  5/16/2008 PASS
PLANS/APPL TAKEN TO FRONT DESK  5/16/2008 DONE
Inspection Record Card- Fire5/16/2008 5/16/2008 DONE
DetailsPatricia Smith
Telephone call  5/16/2008 DONE
left message w breanna for john lopez at ###-#### - permit ready and fees given
Permit Ready to Issue  5/16/2008 DONE
Application received  4/30/2008  
Plan assigned to (Stephanie)4/30/2008 4/30/2008 DONE
DetailsStephanie L. Cobbley
Case Summary  4/30/2008 DONE