INSP-Final Inspection | 10/15/2008 | 10/15/2008 | 10/15/2008 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in | 6/25/2008 | 6/25/2008 | 6/25/2008 | P | PART |
Forrest France
|
|
|
Verified relocated pendent at the reception entry, tenting at the wet piping is acceptable, OH install is okay for cover at the sheetrock ceilings this TI only.
|
Override - Parcel Holds | 6/25/2008 | 1/1/1900 | 6/25/2008 | | |
|
|
|
rough in only
|
INSP-Sprinkler Rough-in | 6/23/2008 | 6/23/2008 | 6/23/2008 | P | PART |
Forrest France
|
|
|
See city stamped plan set for location of one overspaced head at the entry vestibule to be relocated, tenting is not completed for wet system cold cavity protection at this time, remainder of OH install at the tenant area is satisfactory although not yet approved for cover.
|
Override - Parcel Holds | 6/23/2008 | 1/1/1900 | 6/23/2008 | | |
|
|
|
for fire not bld
|
Issue and Print Permit | | | 5/30/2008 | | DONE |
|
|
|
|
Plan assigned to (SAM) | 5/8/2008 | | 5/27/2008 | | PASS |
Patricia Smith
|
|
|
5/27/2008 11:41:59 P_S - activity updated through activity FIRA22 from case FIR08-00327.
|
Inspection Record Card- Fire | 5/27/2008 | | 5/27/2008 | | DONE |
Patricia Smith
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/27/2008 | | DONE |
|
|
|
|
Telephone call | | | 5/27/2008 | | DONE |
|
|
|
left message with sam for greg johnson at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 5/27/2008 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/8/2008 | | 5/22/2008 | | PASS |
|
|
|
plans are approved
|
Application received | | | 5/8/2008 | | |
|
|
|
|
Pending Assignment by SAM | 5/8/2008 | | | | |
|
|
|
|