Permit Information
Permit NumberFIR08-00332
StatusFinaled
Name MICRON TECHNOLOGY INC FP
Site Address 8000 S FEDERAL WAY
Project NameAMHS Phase 3 B24D
Customer NumberC12314
ePlanReview 
Description
Fire Sprinkler System: C12314 B24D Demo and Relo. Sprinklers for AMHS Installation. B24C East: To demo 2 ssp heads and piping and install 4 new ssp heads and piping. B24D West" demo 56 ssp heads and piping and install 52 new pendent heads.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/9/200812/10/200812/10/2008APASS
DetailsForrest France
Fire sprinkler permit work finaled, noted corrections verified for completion.
INSP-Final Inspection11/5/200811/6/200811/6/2008AFAIL
DetailsForrest France
See locations marked on cleanroom plan copies for areas in need of adjustment due to heads obstructed by adjacent equipment and supports at the ceilings.
INSP-Final Inspection10/31/200811/5/200811/5/2008ADEFR
DetailsForrest France
Phone #: ###-#### Internet Inspection Request from: Wayne Berry
Issue and Print Permit  8/21/2008 DONE
PLANS/APPL TAKEN TO FRONT DESK  8/20/2008 DONE
Sprinkler Plan Check  7/30/2008 PASS
On site review and approval of revised plans done by T. Cobbley.
Meeting  7/2/2008 DONE
Site review of new OH material handling conveyors which create a sprinkler obstruction situation, with Paul Marcolina and Steve Murdock. Depth and extent of OH conveyor equipment preclude meeting the NFPA 13, 8.5.5 Obstruction to Sprinkler Discharge spacing requirements. They propose using the Obstructed Construction requirements, but the nature of the obstructions does not fit the Construction Obstruction definitions of 3.7. They agreed to investigate out how their other facility protected similar conveyor obstructions, obtain FM's insurance recommendations, and look into the possibility of installing baffles to simulate construction obstructions as defined by NFPA 13, 3.7 so as to allow use of those requirements. SLR
Sprinkler Plan Check  6/19/2008 FAIL
Initial plan review failed - does not meet spacing requirements of NFPA 13 for Obstructions. Referred to S. Rogers.
Plan assigned to (Scott)  5/8/2008 DONE
DetailsSam Rogers
This permit was created on the web by Paul Marcolina
Plan assigned to (SAM)  5/8/2008 DONE
This permit was created on the web by Paul Marcolina