Information based on query as of Sunday, August 18, 2024.
Permit Information
Permit NumberFIR08-00341
StatusFinaled
Name SIMPLEX GRINNELL
Site Address 700 N ANCESTOR PL
Project NameSuperValu Westpark Data Center
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace an existing 4010 FACP with a new 4100U in the existing building, and to add a new 4100U FACP in the new building expansion. Scope of this permit is also to include a full manual fire alarm system, monitoring and releasing an existing preaction system, two new pre-action systems, and a new clean-agent system. Scope to include monitoring existing, as well as new, HVAC monitoring and in-duct detectors. The panels are networked to operate as one panel.

12-9-08 PLAN MODIFICATION:
This plan modification of the original permit scope is to utilize one 4100U, rather than two. In addition, smoke detectors are being added and/or relocated above the ceiling in Data Room 160 because of beam obstructions.

Associated building permit for reference: BLD07-03132 (SuperValu Westpark Data Center Expansion and Remodel) To demo and remodel the western portion of this existing data center and to constructed a new 16,150 square foot, one story addition at the northwest and west sides of the existing building. This permit also includes the construction of a 140'x45' masonry wall enclosure for new electrical equipment. The new addition will include a new data storage area, a new receiving area and three new UPS/electrical rooms. The remodeled area will include a rearranged office area, a meeting room, operations command center, storage, mechanical and staging areas. This building is fully fire sprinkled. The sprinklers are used for area increase. All construction per the approved plans and attached comment list. JCM
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/8/2009 DONE
Plans taken to records to scan
INSP-Final Inspection2/3/20092/3/20092/3/2009PPASS
DetailsTroy Cobbley
Permit finaled. A tree was removed from infront of the strobe in the employee breakroom.
INSP-Alarm Testing12/24/200812/31/200812/31/2008ACANC
DetailsTroy Cobbley
mark Phone #: ###-####
INSP-Alarm Testing12/24/200812/30/200812/30/2008ACANC
DetailsTroy Cobbley
mark Phone #: ###-####
INSP-Alarm Testing12/24/200812/29/200812/29/2008AFAIL
DetailsTroy Cobbley
Need the north red alarm strobe repaired and tested, the new duct smoke detector does not shut down the hvac unit and the fire alarm system needs to be finished in the existing east rooms.
INSP-Final Inspection12/23/200812/24/200812/24/2008APART
DetailsForrest France
Alarm and supervisory conditions for both the new sprinkler risers and the two existing risers tested today, functionality testing passed for all four preaction systems, noted the wall mounted PIV for the new west riser is not adjusted correctly to activate within 1/5 of valve closure, also discovered the outside bell at the existing riser is not operational. Discussed SD locations at beam pockets in the corridor and mounting heights of existing pull stations at the east side of the building.
Case Summary  12/23/2008 DONE
DetailsAlexandra L. DeYoung
PLANS/APPL TAKEN TO FRONT DESK  12/23/2008 DONE
Inspection Record Card- Fire12/23/2008 12/23/2008 DONE
Details
Telephone call  12/23/2008 DONE
Details
t/c w charlie bayne at ###-#### - permit ready and fees given
Permit Ready to Issue  12/23/2008 DONE
Details
CHANGE STATUS TO (ISS)  12/23/2008 DONE
DetailsAlexandra L. DeYoung
Alarm Plan Check12/18/2008 12/23/2008 PASS
DetailsSam Rogers
Plan revision #4 adding access control magnetic door lock release, RTU/HVAC shut down, modified 2 red clean agent strobes to 15 cd.
INSP-Alarm Testing12/16/200812/18/200812/18/2008AFAIL
DetailsTroy Cobbley
No inspection was performed today but a correction notice was left with Mark. The correction notice lists: Provide resubmittals showing the door mag/locks and test the interconnection with the fire alarm panel, the two amber strobes inside of and the two red strobes outside of the large preaction room are the incorrect candella as per the plans, all of the alarm interconnections with the existing and new preaction sprinkler systems need to be tested, the graphic annunciator is non-functional and needs to be tested/repaired, the alarm system for the large preaction room needs tested, the facp needs to be re-programmed to operate the preaction valves per review comment #3, provide tests reports reflecting the devices already tested as marked on the resubmitted plans and provide a completed/installed fire alarm system that is fully functional with a clear panel as per IFC 907.18.
Plan resubmittals received  12/18/2008 DONE
DetailsAlexandra L. DeYoung
Plan mod rec'd- one copy of app and one copy of sheets 1-9; taken to fire review
Plan assigned to (Stephanie)12/18/2008 12/18/2008 DONE
DetailsPatricia Smith
INSP-Alarm Testing12/16/200812/17/200812/17/2008ADONE
DetailsTroy Cobbley
Additional initiating devices were tested today. See the city approved plans for devices. The fire alarm plans need to be resubmitted showing the door magnets. Also the fire alarm panel is having undefined troubles showing up and the graphic annunciator is not operating. No more testing will be done until the fire alarm system is completely functional.
INSP-Alarm Testing12/15/200812/16/200812/16/2008ADONE
DetailsTroy Cobbley
See the city approved plans for devices tested. The audio/visuals were also tested. The interconnections between the NAC panels tested ok. The existing NAC panel in the mechanical room needs 12.7 ah batteries. Supervision failed on the 110ah battery backup.
CHANGE STATUS TO (ISS)  12/10/2008 DONE
(F) Reprint permit  12/10/2008 DONE
Alarm Plan Check  12/9/2008 PASS
See comments - contractor to keep previously approved set (review dated 5-16-08) in addition to these approved plans on job site. Call plan reviewer with any questions.
PLANS/APPL TAKEN TO FRONT DESK  12/9/2008 DONE
Telephone call  12/9/2008 DONE
Left a message for Charlie Bayne letting him know that they would need to keep the previously approved set (dated 5-16-08) as well as this newly approved plan modification on the job site. I explained in the message that the same items clouded for the first approved set were not clouded in this plan modification and that the inspector would not know what to look at. I asked that future submittals keep the same clouded areas consistent throughout the approval process. I also noted this in the comments for the inspector.
Inspection Record Card- Fire12/9/2008 12/9/2008 DONE
Details
Telephone call  12/9/2008 DONE
Details
left message w ursula for charlie bayne at ###-#### - permit ready for pickup - no fees
Permit Ready to Issue  12/9/2008 DONE
Plan resubmittals received  12/3/2008  
DetailsBarbara Stitt
Plan assigned to (Stephanie)12/3/2008 12/3/2008 DONE
DetailsStephanie L. Cobbley
FIR-Aging Inspection8/15/20088/15/20088/15/2008 NR
DetailsTroy Cobbley
Work is in progress
Alarm Plan Check  5/16/2008 PASS
PLANS/APPL TAKEN TO FRONT DESK  5/16/2008 DONE
Inspection Record Card- Fire5/16/2008 5/16/2008 DONE
DetailsPatricia Smith
Telephone call  5/16/2008 DONE
t/c w charlie bayne at ###-#### - permit ready and fees given
Permit Ready to Issue  5/16/2008 DONE
Issue and Print Permit  5/16/2008 DONE
Telephone call  5/15/2008 DONE
Phone call with Charlie Bayne. Plans had been denied due to matrix representation of double interlock for the preaction system. He stated that he would revise the matrix and that no devices needed to be changed and asked if he could just fax in or email a new set of Matrices to attach to the plans. I let him know that was fine as long as that is all that would change due to the interlock issue.
Alarm Plan Check  5/14/2008 FAIL
Plans denied. See review comments
Miscellaneous action  5/14/2008 DONE
Faxed review comments to SimplexGrinnell
Application received  5/13/2008  
Plan assigned to (Stephanie)5/13/2008 5/13/2008 DONE
DetailsStephanie L. Cobbley