INSP-Final Inspection | 8/25/2008 | 8/26/2008 | 8/26/2008 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 8/21/2008 | 8/22/2008 | 8/22/2008 | A | FAIL |
Forrest France
|
|
|
Need to provide inspectors test connections per NFPA 13D 2007 7.2.4 and 7.2.5.
|
INSP-Final Inspection | 8/18/2008 | 8/19/2008 | 8/19/2008 | P | FAIL |
Forrest France
|
|
|
Provide "911" signs at the outside bells, noted light fixture obstructions at some locations, provide missing head boxes and stock of spare sprinklers, secure signage at the control valve for the north unit, need to complete alarm bell testing, provide plans and review notes on site for verification of conditions met at next inspection, missing NFPA 25's.
|
INSP-Sprinkler Rough-in | 6/16/2008 | 6/16/2008 | 6/16/2008 | A | PART |
Forrest France
|
|
|
OH rough-in okayed for cover as indicated for units one, two and three, first and second floors.
|
INSP-Sprinkler Rough-in | 6/10/2008 | 6/11/2008 | 6/11/2008 | P | PART |
Forrest France
|
|
|
Corrections listed at the previous inspection are finished, overhead rough-in is approved for cover.
|
INSP-Sprinkler Rough-in/Hydro | 6/9/2008 | 6/10/2008 | 6/10/2008 | A | FAIL |
Forrest France
|
|
|
Sprinkler heads at each first floor unit under the stairways are overspaced, 2nd floor mid unit hallway head needs relocated due to overspacing, remainder of flow testing passed, tenting at the attic spaces is satisfactory.
|
INSP-Sprinkler Rough-in | 6/6/2008 | 6/9/2008 | 6/9/2008 | A | CANC |
Troy Cobbley
|
|
|
dave Phone #: ###-####
|
INSP-Sprinkler Rough-in | 6/5/2008 | 6/6/2008 | 6/6/2008 | A | FAIL |
Forrest France
|
|
|
The second floor middle and left end units have been sheetrocked prior to overhead rough-in inspection, completed satisfactory flow testing and OH inspection for the right side unit 1st and 2nd floors, noted missing flow switch and outside bell at all units, discussed shoutoff valve signage and head box placement.
|
Plan assigned to (OutSourced) | 5/21/2008 | | 6/5/2008 | | PASS |
|
|
|
Plans & Calculations are Approved by Bryan Johnson
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/5/2008 | | DONE |
Cathy Brown
|
|
|
|
Inspection Record Card- Fire | 6/5/2008 | | 6/5/2008 | | DONE |
Cathy Brown
|
|
|
|
Issue and Print Permit | | | 6/5/2008 | | DONE |
|
|
|
|
Application received | | | 5/21/2008 | | |
|
|
|
|
Case Summary | | | 5/21/2008 | | DONE |
|
|
|
|