Miscellaneous action | | | 5/8/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 8/27/2008 | 8/27/2008 | 8/27/2008 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 8/22/2008 | 8/26/2008 | 8/26/2008 | A | FAIL |
Troy Cobbley
|
|
|
The manual pull station located at the southeast storage room exit doors needs to be deleted and updated plans provided and an updated map at the facp. This door is not required and can be deleted.
|
INSP-Final Inspection | 8/21/2008 | 8/22/2008 | 8/22/2008 | A | FAIL |
Troy Cobbley
|
|
|
Provide an updated map, provide as-builts with corrected addresses, provide monitoring station printout, install the two remote annunciators as shown on the plans and remove the plastic tubes from the duct smoke detector
|
Issue and Print Permit | | | 6/12/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/10/2008 | | 6/10/2008 | | DONE |
|
|
|
|
Telephone call | | | 6/10/2008 | | DONE |
|
|
|
left message w margo for john lopez at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 6/10/2008 | | DONE |
|
|
|
|
Alarm Plan Check | 6/9/2008 | | 6/9/2008 | | PASS |
Stephanie L. Cobbley
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/9/2008 | | DONE |
|
|
|
|
Plan resubmittals received | | | 6/5/2008 | | |
Stephanie L. Cobbley
|
|
|
Received application and three copies of FA-1, FA-2, and submittal info; taken to fire review
|
Plan assigned to (Stephanie) | 6/5/2008 | | 6/5/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | | | 5/28/2008 | | FAIL |
|
|
|
Red lined plans available for pick up at front counter
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/28/2008 | | DONE |
|
|
|
Plans denied, 1st review.
|
Miscellaneous action | | | 5/28/2008 | | DONE |
|
|
|
Review comments faxed to Fire Sentry Systems
|
Application received | | | 5/21/2008 | | |
|
|
|
|
Plan assigned to (Stephanie) | 5/21/2008 | | 5/21/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Case Summary | | | 5/21/2008 | | DONE |
|
|
|
|