Miscellaneous action | | | 3/10/2009 | | DONE |
|
|
|
Sent for archiving
|
Miscellaneous action | | | 3/10/2009 | | DONE |
|
|
|
Sent for archiving
|
INSP-Final Inspection | 1/14/2009 | 1/16/2009 | 1/16/2009 | A | PASS |
Forrest France
|
|
|
Final fire sprinkler inspection and acceptance testing completed satisfactory, permit finaled.
|
INSP-Sprinkler Rough-in | 1/15/2009 | 1/15/2009 | 1/15/2009 | P | PART |
Forrest France
|
|
|
Correction notice items per last inspection are finished, verified resubmitted plans for field changes, rough-in passed.
|
INSP-Sprinkler Rough-in/Hydro | 1/14/2009 | 1/15/2009 | 1/15/2009 | A | PART |
Forrest France
|
|
|
OH hydrostatic testing completed satisfactory.
|
INSP-Final Inspection | 1/14/2009 | 1/15/2009 | 1/14/2009 | P | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 1/14/2009 at 11:08:00 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jan 14 2009 11:25AM.
|
INSP-Sprinkler Rough-in/Hydro | 12/30/2008 | 12/31/2008 | 12/31/2008 | P | FAIL |
Forrest France
|
|
|
Approved plan set on site does not match floorplan or actual installation including heads and piping beneath three mezzanines, added mech. tees and uprights, noted one work area overspaced beyond 130 ft2, missing forward flow appuratus at the riser, need PRV due to grid system, hydrostatic test postponed until changes are approved.
|
INSP-Sprinkler Rough-in/Hydro | 12/29/2008 | 12/30/2008 | 12/30/2008 | P | CANC |
Troy Cobbley
|
|
|
To be rescheduled
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/26/2008 | | DONE |
Cathy Brown
|
|
|
|
Inspection Record Card- Fire | 11/26/2008 | | 11/26/2008 | | DONE |
Cathy Brown
|
|
|
|
Telephone call | | | 11/26/2008 | | |
Cathy Brown
|
|
|
tlk to tony larson ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 11/26/2008 | | DONE |
Cathy Brown
|
|
|
|
(F) Reprint permit | | | 11/26/2008 | | |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 11/26/2008 | | DONE |
Barbara Stitt
|
|
|
|
Sprinkler Plan Check | 11/18/2008 | | 11/22/2008 | | PASS |
|
|
|
Note: This was the 3rd review of these previously approved plans. There were 4 heads added. Plans are approved by Bryan Johnson
|
(F) Reprint permit | | | 11/18/2008 | | |
|
|
|
|
Plan resubmittals received | | | 11/18/2008 | | |
|
|
|
received "4" sets of applications with "4" sets of plans- put plans on fire shelf
|
INSP-Supply line flush | 7/7/2008 | 7/10/2008 | 7/10/2008 | A | PART |
Forrest France
|
|
|
UG fire supply line flush completed acceptable.
|
INSP-Supply line flush | 7/2/2008 | 7/8/2008 | 7/8/2008 | A | PART |
Forrest France
|
|
|
Field inspection was intended for an UG hydrostatic test. Hydro completed satisfactory-testing passed.
|
INSP-Sprinkler Rough-in/Hydro | 7/8/2008 | 7/8/2008 | 7/8/2008 | P | PART |
Forrest France
|
|
|
UG fire supply line installation is approved for bury.
|
INSP-Supply line flush | 7/3/2008 | 7/7/2008 | 7/7/2008 | P | NR |
Forrest France
|
|
|
tony/brian ###-#### Note: 1:00 Phone #: ###-#### Inspection rescheduled per conversation with contractor.
|
INSP-Supply line flush | 7/1/2008 | 7/7/2008 | 7/2/2008 | A | CANC |
Forrest France
|
|
|
Scheduled by a contractor via Hello! on 7/1/2008 at 11:35:54 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jul 2 2008 7:16AM.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/19/2008 | | DONE |
|
|
|
|
Telephone call | | | 6/19/2008 | | DONE |
|
|
|
t/c tony larson at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 6/19/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/19/2008 | | DONE |
|
|
|
|
Plan assigned to (OutSourced) | 5/30/2008 | | 6/19/2008 | | PASS |
Patricia Smith
|
|
|
6/19/2008 09:11:47 P_S - activity updated through activity FIRA22 from case FIR08-00369.
|
Inspection Record Card- Fire | 6/19/2008 | | 6/19/2008 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/9/2008 | | 6/16/2008 | | PASS |
|
|
|
plans are approved
|
Plan resubmittals received | | | 6/9/2008 | | |
Tisha Gallop
|
|
|
Received four copies of appliation, submittal packet, calcs, product info, and sheet FP1 of 1; taken to fire review
|
Sprinkler Plan Check | 5/30/2008 | | 6/5/2008 | | FAIL |
|
|
|
These plans were denied do to lack of or missing information. Upon request, the denied set of plans may be retrieved from my office for salvage with in 5 working days.
|
Application received | | | 5/27/2008 | | |
|
|
|
|
Case Summary | | | 5/27/2008 | | DONE |
|
|
|
|
Pending Assignment by SAM | 5/27/2008 | | | | |
|
|
|
|