INSP-Final Inspection | 7/9/2008 | 7/9/2008 | 7/10/2008 | P | PASS |
Forrest France
|
|
|
Under ground completed, See Forrest notes for under ground on FIR08-00370. KR
|
INSP-Sprinkler Rough-in/Hydro | 6/24/2008 | 6/25/2008 | 6/25/2008 | A | FAIL |
Forrest France
|
|
|
Need to add one upright head due to overspacing, missing hanger at one armover, FDC is obstructed by landscaping (GC agreed to remove plants as necessary), SW heads at dormers are okay, remainder of rough-in is acceptable.
|
Issue and Print Permit | | | 6/20/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/19/2008 | | 6/19/2008 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/19/2008 | | DONE |
|
|
|
|
Telephone call | | | 6/19/2008 | | DONE |
|
|
|
left vm for lillie at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 6/19/2008 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/27/2008 | | 6/17/2008 | | PASS |
|
|
|
plans are approved w/ conditions
|
Early Start | | | 6/3/2008 | | DONE |
|
|
|
Approved Early Start request subject to limitations of work stipulated in letter. Faxed approval to Shiloh. Doc attached.
|
Early Start | | | 5/30/2008 | | DONE |
|
|
|
Received fax for early start request from Randy Knutson. Sam Rogers to review.
|
Application received | | | 5/27/2008 | | |
|
|
|
|
Pending Assignment by SAM | 5/27/2008 | | | | |
|
|
|
|