INSP-Final Inspection | 10/13/2008 | 10/13/2008 | 10/13/2008 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 10/10/2008 | 10/10/2008 | 10/13/2008 | P | CANC |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 10/10/2008 at 8:38:50 AM. Contact: ###-####.
|
INSP-Sprinkler Rough-in/Hydro | 7/9/2008 | 7/9/2008 | 7/9/2008 | P | PART |
Troy Cobbley
|
|
|
Changes made per last inspection. OK to cover. KR
|
INSP-Sprinkler Rough-in/Hydro | 7/8/2008 | 7/8/2008 | 7/8/2008 | P | FAIL |
Troy Cobbley
|
|
|
As-builts need to be provided showing the pipe route changes. See the city approved plans for locations where sprinkler pendants are located too close, too far off of walls and where no sprinkler protection has been provided. One location needs the tenting improved.
|
Issue and Print Permit | | | 6/18/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/17/2008 | | 6/17/2008 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/17/2008 | | DONE |
|
|
|
|
Telephone call | | | 6/17/2008 | | DONE |
|
|
|
t/c w jim danes at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 6/17/2008 | | DONE |
|
|
|
|
Sprinkler Plan Check | 5/28/2008 | | 6/13/2008 | | PASS |
|
|
|
plans are approved
|
Case Summary | | | 5/28/2008 | | DONE |
|
|
|
|
Application received | | | 5/28/2008 | | |
|
|
|
|
Pending Assignment by SAM | 5/28/2008 | | | | |
|
|
|
|