Permit Information
Permit NumberFIR08-00397
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 9050 W OVERLAND RD Unit: 100
Project NameBROWN MACKIE COLLEGE T.I.
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install notification devices and duct detectors due to a tenant improvement that will cover a portion of the 1st and the entire 2nd floor. The shell was approved under permit number FIR06-00507 which included the sprinkler monitoring, shell notification, and elevator recall functions.

08-12-08 PLAN MODIFICATION: additional notification devices were provided due to full height walls being added, some minor circuiting changes in the field, a candela increased due to mounting issues, and based on field inspection door holders were added.

08-18-08 PLAN MODIFICATION: Added a remote power supply and re-landed existing circuits (as-is) onto the new remote power supply NACs due to synchronization problems.

Associated building permit: BLD08-00984 (BROWN MACKIE COLLEGE - ANDERSON BLACK EAGLE BLDG -1ST & 2ND FLRS) To construct a 25,612 sq.ft. medical education facility covering areas on 2 stories (14,672 s.f. 1st / 10,940 s.f. 2nd) of an existing shell building per approved plans and CUP08-00056. Work includes select interior demolition, construction of non-combustible framed walls to create instruction & demonstration/practice classrooms & labs; administrative office's and support areas; study/library, student lounge, accessible restrooms and accessible elements throughout; suspended ACT & sheetrock ceilings; electrical, mechanical, plumbing, sprinkler & alarm systems work; millwork and finishes throughout. Drs
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/11/2009 DONE
Plans taken to records to scan
INSP-Final Inspection8/21/20088/21/20088/21/2008PPASS
DetailsTroy Cobbley
Permit finaled
(F) Reprint permit  8/20/2008 DONE
CHANGE STATUS TO (ISS)  8/20/2008 DONE
DetailsBarbara Stitt
Inspection Record Card- Fire8/19/2008 8/19/2008 DONE
Details
Telephone call  8/19/2008 DONE
Details
left message w craig for jason minnick at ###-#### - permit ready and no fees due
Permit Ready to Issue  8/19/2008 DONE
Details
Plan assigned to (Stephanie)8/14/2008 8/18/2008 DONE
DetailsStephanie L. Cobbley
Plan resubmittals received  8/18/2008 DONE
DetailsBarbara Stitt
Alarm Plan Check  8/18/2008 PASS
PLANS/APPL TAKEN TO FRONT DESK  8/18/2008 DONE
INSP-Final Inspection8/12/20088/13/20088/13/2008AFAIL
DetailsTroy Cobbley
All of the previous deficiencies have been corrected. Once we were able to test the audio/visual devices we found that the second floor horns are not syncronized as required per NFPA 72 - 6.8.6.5.3. The duct smoke detectors tested ok.
Alarm Plan Check  8/12/2008 PASS
PLANS/APPL TAKEN TO FRONT DESK  8/12/2008 DONE
Plan assigned to (Stephanie)8/12/2008 8/12/2008 DONE
DetailsBarbara Stitt
Plan resubmittals received  8/12/2008 DONE
Inspection Record Card- Fire8/12/2008 8/12/2008 DONE
Details
Telephone call  8/12/2008 DONE
Details
t/c w jason minnick at ###-#### - permit ready and no fees due
Permit Ready to Issue  8/12/2008 DONE
Details
(F) Reprint permit  8/12/2008 DONE
CHANGE STATUS TO (ISS)  8/12/2008 DONE
DetailsTisha Gallop
picked up plan mod
Plan assigned to (Stephanie)6/9/2008 8/12/2008 DONE
DetailsStephanie L. Cobbley
INSP-Final Inspection8/8/20088/11/20088/11/2008AFAIL
DetailsTroy Cobbley
The job site approved plan set was not on the job site. A strobe in the first floor area as marked on the plans is blocked by walls. There are many strobes on the second floor that are overspaced. The fire alarm contractor needs to review the spacing on all of the second floor strobes for code compliance. I pointed out a note on the review comments about the minimum voltage allowed from the fire alarm panel that is to be verified prior to my next inspection. Also plans need to be resubmitted showing the door magnets (access controlled egress doors) and their interconnection to the FACP. Basically no testing was performed.
INSP-Final Inspection8/7/20088/8/20088/8/2008PCANC
DetailsTroy Cobbley
Troy, Please call as soon as you know an approximate time. Thank You. Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
Issue and Print Permit  6/16/2008 DONE
Alarm Plan Check  6/13/2008 PASS
See review comments
PLANS/APPL TAKEN TO FRONT DESK  6/13/2008 DONE
Inspection Record Card- Fire6/13/2008 6/13/2008 DONE
Details
Telephone call  6/13/2008 DONE
Details
t/c w jason minnick at ###-####- permit ready and fees given
Permit Ready to Issue  6/13/2008 DONE
Details
Application received  6/9/2008  
Case Summary  6/9/2008 DONE