Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 8/21/2008 | 8/21/2008 | 8/21/2008 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
(F) Reprint permit | | | 8/20/2008 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 8/20/2008 | | DONE |
Barbara Stitt
|
|
|
|
Inspection Record Card- Fire | 8/19/2008 | | 8/19/2008 | | DONE |
|
|
|
|
Telephone call | | | 8/19/2008 | | DONE |
|
|
|
left message w craig for jason minnick at ###-#### - permit ready and no fees due
|
Permit Ready to Issue | | | 8/19/2008 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 8/14/2008 | | 8/18/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Plan resubmittals received | | | 8/18/2008 | | DONE |
Barbara Stitt
|
|
|
|
Alarm Plan Check | | | 8/18/2008 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/18/2008 | | DONE |
|
|
|
|
INSP-Final Inspection | 8/12/2008 | 8/13/2008 | 8/13/2008 | A | FAIL |
Troy Cobbley
|
|
|
All of the previous deficiencies have been corrected. Once we were able to test the audio/visual devices we found that the second floor horns are not syncronized as required per NFPA 72 - 6.8.6.5.3. The duct smoke detectors tested ok.
|
Alarm Plan Check | | | 8/12/2008 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/12/2008 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 8/12/2008 | | 8/12/2008 | | DONE |
Barbara Stitt
|
|
|
|
Plan resubmittals received | | | 8/12/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/12/2008 | | 8/12/2008 | | DONE |
|
|
|
|
Telephone call | | | 8/12/2008 | | DONE |
|
|
|
t/c w jason minnick at ###-#### - permit ready and no fees due
|
Permit Ready to Issue | | | 8/12/2008 | | DONE |
|
|
|
|
(F) Reprint permit | | | 8/12/2008 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 8/12/2008 | | DONE |
Tisha Gallop
|
|
|
picked up plan mod
|
Plan assigned to (Stephanie) | 6/9/2008 | | 8/12/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
INSP-Final Inspection | 8/8/2008 | 8/11/2008 | 8/11/2008 | A | FAIL |
Troy Cobbley
|
|
|
The job site approved plan set was not on the job site. A strobe in the first floor area as marked on the plans is blocked by walls. There are many strobes on the second floor that are overspaced. The fire alarm contractor needs to review the spacing on all of the second floor strobes for code compliance. I pointed out a note on the review comments about the minimum voltage allowed from the fire alarm panel that is to be verified prior to my next inspection. Also plans need to be resubmitted showing the door magnets (access controlled egress doors) and their interconnection to the FACP. Basically no testing was performed.
|
INSP-Final Inspection | 8/7/2008 | 8/8/2008 | 8/8/2008 | P | CANC |
Troy Cobbley
|
|
|
Troy, Please call as soon as you know an approximate time. Thank You. Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
Issue and Print Permit | | | 6/16/2008 | | DONE |
|
|
|
|
Alarm Plan Check | | | 6/13/2008 | | PASS |
|
|
|
See review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/13/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 6/13/2008 | | 6/13/2008 | | DONE |
|
|
|
|
Telephone call | | | 6/13/2008 | | DONE |
|
|
|
t/c w jason minnick at ###-####- permit ready and fees given
|
Permit Ready to Issue | | | 6/13/2008 | | DONE |
|
|
|
|
Application received | | | 6/9/2008 | | |
|
|
|
|
Case Summary | | | 6/9/2008 | | DONE |
|
|
|
|