Permit Information
Permit NumberFIR08-00402
StatusFinaled
Name PERAS PLUMBING SERVICE
Site Address 10269 W ALPINE MEADOW ST
Project NameCornell Residence
Customer Number 
ePlanReview 
Description
10/30/08 Revised FIR Sprinkler Scope:
These previously approved plans were resubmitted As-Built for approval. The revisions have been noted as Rev #4 and dated 10/02/08.
10/22/08 Revised FIR Sprinkler Scope:
These previously approved plans were resubmitted to include a booster pump installation. The booster pump enabled the system to meet the flow and pressure requirements. In addition, several pipe size changes were made in order to assure the required flow (gpm) as designed.
09/12/08 Revised FIR Sprinkler Scope:
These previously approved plans were resubmitted to include a booster pump installation. The booster pump enabled the system to meet the flow and pressure requirements. In addition to the pump, the contractor changed the ½” riser supply sections of piping to 1”. These revisions were noted on the plans as Revision #3 and dated 09-08-08. Revised FIR Sprinkler Scope: These previously approved plans were resubmitted to include a booster pump installation. The booster pump enabled the system to meet the flow and pressure requirements. In addition to the pump, the contractor changed the ½” riser supply sections of piping to 1”. These revisions were noted on the plans as Revision #3 and dated 09-08-08. FIR Sprinkler Scope: Install a new 13D approved multi purpose piping system (Uponor , Wirsbo ) fire sprinkler system through out the two story single family dwelling to include a single row of side wall heads in the garage along the common. The system will be supplied from a 1” poly line. (by others) All fire sprinkler work shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to BLD08-00813.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  3/10/2009 DONE
Sent for archiving
INSP-Final Inspection10/31/200810/31/200810/31/2008PPASS
DetailsTroy Cobbley
permit finaled
(F) Reprint permit  10/31/2008 DONE
CHANGE STATUS TO (ISS)  10/31/2008 DONE
Sprinkler Plan Check10/24/2008 10/30/2008 PASS
Details
Plans are approved by Bryan Johnson
PLANS/APPL TAKEN TO FRONT DESK  10/30/2008  
DetailsCathy Brown
Issue and Print Permit  10/30/2008 DONE
Inspection Record Card- Fire10/30/2008 10/30/2008 DONE
DetailsCathy Brown
PLANS/APPL TAKEN TO FRONT DESK  10/30/2008 DONE
DetailsCathy Brown
Permit Ready to Issue  10/30/2008 DONE
DetailsCathy Brown
Plan resubmittals received  10/24/2008  
Details
Plan assigned to (OutSourced)10/22/2008 10/22/2008 DONE
DetailsCathy Brown
Plan resubmittals received  10/6/2008  
Plan modifcation; rec'd 1 copy of application, 6 copies of submittal packet, and 3 copies of pages f100 and f101, taken to fire review
INSP-Sprinkler Rough-in9/16/20089/16/20089/17/2008PPART
DetailsTroy Cobbley
The bucket test passed. The two head area flowed 31 gallons and the single head area flowed 22 gallons. I gave the ok to cover the piping with the condition that as-built plans and hydraulic calculations are re-submitted to the city. This is due to the interconnecting piping to and between the four manifolds, as installed, does not match the city approved plans.
(F) Reprint permit  9/16/2008 DONE
CHANGE STATUS TO (ISS)  9/16/2008 DONE
INSP-Sprinkler Rough-in/Hydro9/12/20089/15/20089/15/2008AFAIL
DetailsTroy Cobbley
The updated plans were not on site but Sam Rogers and I went ahead and conducted the single and the double head flow verifications. The single head test passed in both the single head remote area and when just a single head was flowed in the two head area. But when the two head test was performed not enought water was put out. Infact not enough water was available when measured right at the pump. No rough-in inspection of the piping has been performed yet.
Inspection Record Card- Fire9/15/2008 9/15/2008 DONE
Details
PLANS/APPL TAKEN TO FRONT DESK  9/15/2008  
Details
Telephone call  9/15/2008 DONE
Details
left vm for dave pera at ###-#### - permit ready and fees given
Permit Ready to Issue  9/15/2008 DONE
Details
Sprinkler Plan Check9/8/2008 9/12/2008 PASS
Details
plans are approved - This was the third review of these previously approved plans. The plans were resubmitted due to modifications made in the field during construction. Three heads within the remote areas were affected as a result.
Plan resubmittals received  9/8/2008  
received 1 fire sprinkler application, 6 copies of fire safty system, and 3 plans stamped as re-subs and put in fire slot for Brian Johnson to review///DLD
INSP-Sprinkler Rough-in8/28/20088/29/20088/29/2008AFAIL
DetailsTroy Cobbley
The plans have not been resubmitted showing the additional piping and the tenting was not complete. No inspection was performed though I did stop at the job site.
INSP-Sprinkler Rough-in/Hydro8/27/20088/28/20088/28/2008AFAIL
DetailsTroy Cobbley
The single head test barely made the 18gpm requirement and the 26.6gpm requirement for the two heads failed. The plans will have to be resubmitted if changes are made that effect piping or hydraulic calculations. Also the piping had not been tented yet.
INSP-Sprinkler Rough-in/Hydro8/26/20088/27/20088/27/2008PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 8/26/2008 at 1:29:31 PM. Contact: ###-####. Inspection cancelled from web by: Alexandra Rahn
Issue and Print Permit  8/25/2008 DONE
Sprinkler Plan Check8/13/2008 8/19/2008 PASS
Details
Plans are approved by Bryan Johnson
PLANS/APPL TAKEN TO FRONT DESK  8/19/2008 DONE
DetailsCathy Brown
Inspection Record Card- Fire8/19/2008 8/19/2008 DONE
DetailsCathy Brown
Telephone call  8/19/2008 DONE
DetailsCathy Brown
tlk to dave pera ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  8/19/2008  
Sprinkler Plan Check7/30/2008 8/13/2008 PEND
Details
Cornel Res. FIR08-00402
This project is on hold pending further information from the contractor.
Plan resubmittals received  7/30/2008  
DetailsSam Rogers
Meeting  7/18/2008 DONE
Front counter meeting with Mitch Cornell, General Contactor/owner of residence. The plumber Dave Pera, listed the G/C's fax number on the application. Both GC and plumber indicate they never received a fax of the review but G/C did access Tidemark where the review was posted on line. Denied plans were held over 5 days by B. Johnson, plan reviewer, as indicated in Tidemark and subsequently discarded per policy. Therefore the plan sets are no longer available. I explained they would be of little use in this situation, since the plans have to be revised and the entire plan set is relatively limited. Sprinkler contractors frequently don't go to the trouble of picking up denied plan sets of this size. Faxed a copy of the review comments to the plumber and gave hard copy to GC; and explained resubmittal to be brought to our permit counter.
Sprinkler Plan Check6/10/2008 7/1/2008 FAIL
Details
These plans were denied due to the lack of or missing information. A complete resubmitted is required ASAP. Upon request, the denied set of plans may be retrieved from my office for salvage.
Note The denied set of plan review comments will be faxed to the contact fax. ###-####
Sprinkler Plan Check6/10/2008 6/26/2008 PEND
Details
Note: Project Alpine Res FIR08-00402 is on hold pending the delivery of missing head and dev ice data, additional copies of the [plans and permit applications.

Application received  6/10/2008  
Pending Assignment by SAM6/10/2008 6/10/2008 DONE
DetailsSam Rogers