Information based on query as of Friday, July 5, 2024.
Permit Information
Permit NumberFIR08-00420
StatusFinaled
Name MOUNTAIN ALARM
Site Address 213 N 9TH ST
Project NameSEDGWICK CENTER-1ST FLR
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add speaker/strobes and relocate existing pull stations to accommodate the tenant improvement. No new initiating devices are indicated as part of this permit scope.

Associated building permit: BLD08-00254 (D. L. EVANS BRANCH BANK - SEDGWICK CENTER - 1ST STORY) (CZC08-00010) This building is fire sprinklered to comply with high-rise provisions. To construct a bank within an existing 4,590 square foot tenant space located on the 1st story of a high-rise building. Work is to include interior nonbearing walls, interior doors, interior windows, a night deposit box, an ATM, suspended gypsum board ceiling, suspended acoustical ceilings, gypsum board soffits, millwork, an exterior window, an exterior metal window panel, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/11/2009 DONE
Plans taken to records to scan
INSP-Final Inspection6/17/20086/18/20086/18/2008APASS
DetailsForrest France
Required corrections verified for completion, fire alarm permit finaled.
INSP-Final Inspection6/17/20086/17/20086/17/2008PPART
DetailsForrest France
Final pending correction of the descriptors at the FACP for three manual pull stations.
INSP-Final Inspection6/16/20086/17/20086/17/2008AFAIL
DetailsForrest France
Repair work and device adjustments are not yet finished, inspection rescheduled.
INSP-Final Inspection6/13/20086/16/20086/16/2008PFAIL
DetailsForrest France
Noted wall mounted notification appliances at six locations are below the min. height AFF per NFPA 72-see fire code review notes item #20, one ceiling mounted a/v needs to be installed per plan, remainder of installation appears acceptable however no functional testing performed due to devices to be relocated/adjusted.
INSP-Sprinkler Rough-in/Hydro6/16/20086/17/20086/16/2008ACANC
DetailsForrest France
Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
Plan assigned to (Stephanie)6/13/2008 6/15/2008 DONE
DetailsStephanie L. Cobbley
INSP-Final Inspection6/13/20086/16/20086/13/2008ACANC
DetailsForrest France
Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
Application received  6/13/2008  
Alarm Plan Check  6/13/2008 PASS
See review comments and annotations on drawings
PLANS/APPL TAKEN TO FRONT DESK  6/13/2008 DONE
Inspection Record Card- Fire6/13/2008 6/13/2008 DONE
Details
Telephone call  6/13/2008 DONE
Details
t/c w bret anderson at ###-#### - permit ready and fees given
Permit Ready to Issue  6/13/2008 DONE
Details
Issue and Print Permit  6/13/2008 DONE