Permit Information
Permit NumberFIR08-00429
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1116 N COLE RD
Project NameBOISE RAQUET AND SWIM CLUB
Customer Number 
ePlanReview 
Description
Revised FIR OH Scope:
The fire sprinkler system was modified in the field in include coverage (8 additional QR heads) at the mezzanine which was added during construction. This revision was noted as Rev A, and dated 09/08/08 FIR OH Scope:
Beginning from an existing 6” supply located with the 1 hour rated riser room located at the SE corner of the building, install a 3” vertical wet riser to serve through out the entire structure including the area beneath the mezzanine. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD08-00664 & UG permit FIR08-00354.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/13/200810/14/200810/14/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/13/200810/13/200810/13/2008PFAIL
DetailsTroy Cobbley
The project is not ready for a final yet.
INSP-Sprinkler Rough-in/Hydro10/10/200810/13/200810/13/2008APASS
DetailsTroy Cobbley
The overhead hydro, underground hydros & fdc flush passed
INSP-Sprinkler Rough-in/Hydro10/8/200810/9/200810/9/2008PCANC
DetailsTroy Cobbley
Note: FDC Flush Phone #: ###-####.
INSP-Sprinkler Rough-in/Hydro10/6/200810/7/200810/7/2008ADONE
DetailsTroy Cobbley
Under ground flush completed. KR
INSP-Sprinkler Rough-in10/6/200810/7/200810/7/2008ADONE
DetailsTroy Cobbley
Remaining areas per Troys last inspection can be covered.KR
INSP-Sprinkler Rough-in9/29/20089/30/20089/30/2008APASS
DetailsTroy Cobbley
The underground piping for the remote FDC and the hose station can be covered except for both ends since thrust blocks, drains and vaults had not been installed yet. As-built plans need to be submitted showing the the positions of the two lines being switched and the remote hose station being relocated to the south.
INSP-Sprinkler Rough-in/Hydro9/24/20089/24/20089/24/2008PPASS
DetailsTroy Cobbley
The underground hydro test passed.
Sprinkler Plan Check9/9/2009 9/24/2008 PASS
Details
These previously approved plans were resubmitted due to changes made in the field during construction. The plans were modified to include 8 additional heads at the mezzanine level to complete coverage. This modification does not appear to adversely affect the previously approved remote area of operation. Plans are approved by Bryan Johnson
PLANS/APPL TAKEN TO FRONT DESK  9/24/2008 DONE
DetailsCathy Brown
Inspection Record Card- Fire9/24/2008 9/24/2008 DONE
DetailsCathy Brown
Telephone call  9/24/2008 DONE
DetailsCathy Brown
lft vm with jess anderson ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  9/24/2008 DONE
DetailsCathy Brown
(F) Reprint permit  9/24/2008 DONE
CHANGE STATUS TO (ISS)  9/24/2008 DONE
INSP-Sprinkler Rough-in9/15/20089/15/20089/15/2008PPASS
DetailsTroy Cobbley
The piping in the mezzanine can be covered. An as-built has been provided showing the extension of the mezzanine and the additional sprinkler protection.
INSP-Sprinkler Rough-in/Hydro8/25/20088/25/20088/25/2008PPART
DetailsForrest France
OH inspection for the court area mains and branchlines only completed today-the lower mezzanine piping is not yet installed, noted one missing EQ brace at the NW corner-location circled on plans, noted high temp. heads in place at the vicinity of the unit heaters, riser is not built.
PLANS/APPL TAKEN TO FRONT DESK  7/1/2008  
DetailsCathy Brown
Inspection Record Card- Fire6/17/2008 7/1/2008  
Details
Telephone call  7/1/2008 DONE
DetailsCathy Brown
tlk to Jeff Anderson ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  7/1/2008 DONE
DetailsCathy Brown
Issue and Print Permit  7/1/2008 DONE
Sprinkler Plan Check6/17/2008 6/30/2008 PASS
Details
Plans & Calculation Approved By Bryan Johnson
Application received  6/17/2008  
Pending Assignment by SAM6/17/2008