Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 8/12/2008 | 8/12/2008 | 8/12/2008 | P | PASS |
Troy Cobbley
|
|
|
Repairs made per last inspection. KR
|
INSP-Final Inspection | 8/7/2008 | 8/7/2008 | 8/7/2008 | A | FAIL |
Troy Cobbley
|
|
|
The 30cd strobe in the yearbook room was not increased as marked on the city approved plans. Also a smoke detector needs to be added in the tele/elect. room next to the elevator shaft on the second floor as marked on the plans. All other smoke detectors have been tested in the scope of work.
|
INSP-Final Inspection | 8/6/2008 | 8/6/2008 | 8/6/2008 | P | CANC |
Forrest France
|
|
|
Overbooked
|
Inspection Record Card- Fire | 6/23/2008 | | 6/23/2008 | | DONE |
|
|
|
|
Telephone call | | | 6/23/2008 | | DONE |
|
|
|
t/c w charlie bayne at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 6/23/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 6/23/2008 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 6/18/2008 | | 6/20/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | | | 6/20/2008 | | PASS |
|
|
|
see review comments and redlines on drawings
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/20/2008 | | DONE |
|
|
|
|
Application received | | | 6/18/2008 | | |
|
|
|
|