Permit Information
Permit NumberFIR08-00434
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 3604 S BANNER AVE
Project NameSTEVE CHRISTENSEN BLDG
Customer Number 
ePlanReview 
Description
Installing 98 LF of 6 inch C900, two MJ elbows, two thrust blocks, 6 feet of ductile iron transition sprinkler piping into riser room, beginning at city 12 inch water main and ending inside new building at riser room location. This permit does not include any overhead installation. This building is being fire sprinklered as a fire protection alternative to an IFC deficiency. New building being constructed under BLD07-02372. * SJA*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  3/10/2009 DONE
Sending for archiving
INSP-Final Inspection1/21/20091/22/20091/22/2009APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection1/21/20091/21/20091/21/2009PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in8/15/20088/18/20088/18/2008APASS
DetailsTroy Cobbley
The underground supply line is ok to bury. The contractor had already buried the thrust block at the in-building riser. I had them dig it out and it appears that it is adequate in size and placement.
INSP-Sprinkler Rough-in/Hydro8/13/20088/14/20088/14/2008APASS
DetailsTroy Cobbley
The under ground hydro test passed.
Issue and Print Permit  8/1/2008 DONE
DetailsTisha Gallop
PLANS/APPL TAKEN TO FRONT DESK  7/25/2008 DONE
DetailsCathy Brown
Override - Parcel Holds  7/25/2008  
Inspection Record Card- Fire7/25/2008 7/25/2008 DONE
DetailsCathy Brown
Telephone call  7/25/2008 DONE
DetailsCathy Brown
tlk to brook nelson ###-#### that permit and fees are ready to be picked up
Override - Parcel Holds  7/25/2008  
Permit Ready to Issue  7/25/2008 DONE
DetailsCathy Brown
Sprinkler Plan Check7/22/2008 7/24/2008 PASS
Details
Plans are approved by Bryan Johnson
Plan resubmittals received  7/22/2008  
Sprinkler Plan Check6/23/2008 6/26/2008 FAIL
Details
These plans were denied due to lack of or missing information. Upon request the denied set of plans may be retrieved from my office for salvage.
Plan resubmittals received  6/24/2008  
DetailsTisha Gallop
Received application and three copies of sheet FP-1; taken to fire review
Application DENIED  6/23/2008 FAIL
DetailsScott Arellano
Does not meet the specific criteria of a fire sprinkler "quick permit." Contacted applicant to resubmit full size plan submittal for fire sprinkler review.
PLANS/APPL TAKEN TO FRONT DESK  6/23/2008 DONE
Application received  6/19/2008  
Pending Assignment by SAM6/19/2008    
Plan assigned to (SAM)6/24/2008