Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 3/3/2009 | 3/5/2009 | 3/5/2009 | A | PASS |
Forrest France
|
|
|
Noted correction items verified for completion, final fire alarm testing passed, permit finaled.
|
INSP-Final Inspection | 3/2/2009 | 3/4/2009 | 3/3/2009 | A | DEFR |
Forrest France
|
|
|
Rescheduled for 3/5 per discussion.
|
INSP-Final Inspection | 2/23/2009 | 2/25/2009 | 2/25/2009 | A | CANC |
Troy Cobbley
|
|
|
To be rescheduled per earl Phone #: ###-####
|
INSP-Final Inspection | 11/4/2008 | 11/5/2008 | 11/5/2008 | P | FAIL |
Forrest France
|
|
|
Noted two non-functional notification devices-locations marked on plans, hall 417 is missing adequate coverage, wall mounted a/v's at all perimeter open office locations are mounted below min. height AFF per NFPA 72, added area SD at the common corridors to be indicated on resubmitted plans. See also review note comments 10 and 11.
|
FIR-Aging Inspection | 10/31/2008 | 10/31/2008 | 11/3/2008 | | DONE |
Forrest France
|
|
|
Pending site inspection request for work completed.
|
Issue and Print Permit | | | 7/15/2008 | | |
|
|
|
|
Plan assigned to (Stephanie) | 6/27/2008 | | 7/14/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | | | 7/14/2008 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/14/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/14/2008 | | 7/14/2008 | | DONE |
|
|
|
|
Telephone call | | | 7/14/2008 | | DONE |
|
|
|
left message w tetia for john lopez at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/14/2008 | | DONE |
|
|
|
|
Case Summary | | | 6/27/2008 | | DONE |
|
|
|
|
Application received | | | 6/27/2008 | | |
|
|
|
|