Permit Information
Permit NumberFIR08-00461
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 851 W FRONT ST
Project NameTHE ASPEN - SHELL
Customer Number 
ePlanReview 
Description
FIR OH Work Scope:
Modify the existing shell protection by adding heads in the mechanical spaces to complete coverage. The plans and calculations were resubmitted as a result of this modification. The dry pipe system volume now exceeds 750 gal due to this modification. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD06-02303.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/13/2010 DONE
Sent to records for scanning.
INSP-Final Inspection4/28/20094/28/20094/28/2009PPASS
DetailsForrest France
Shell sprinkler work okayed for final.
INSP-Sprinkler Rough-in/Hydro4/28/20094/28/20094/28/2009PPART
DetailsForrest France
See activities under project related FIR08-00018 for the majority of inspections completed including the same scope of work for this permit.
Pending Assignment by SAM6/30/2008 3/19/2009 DONE
DetailsTisha Gallop
3/19/2009 14:29:16 LEG - activity updated through activity FIRA158 from case FIR08-00018.
INSP-Sprinkler Rough-in/Hydro1/23/20091/27/20091/27/2009APART
DetailsForrest France
OH sprinkler piping and drops okayed for ceiling cover at the 7th floor common corridor, noted one missing hanger at an armover to be installed today, discussed sw head locations at the cable closets adjacent to the elevator hoistway.
INSP-Sprinkler Rough-in/Hydro1/22/20091/23/20091/23/2009APART
DetailsForrest France
6th floor common corridor overhead install okayed for cover.
INSP-Sprinkler Rough-in7/28/20087/30/20087/30/2008AFAIL
DetailsForrest France
Inspection for overhead fire sprinkler rough-in at the 7th floor failed due to changes in floorplan, piping layout, number, type and location of heads at several areas. Differences between field installation and approved plans are beyond what can normally be accepted on "as-built" drawings, will need to provide approved resubmittal plans including all changes. The installation appears acceptable, however documentation must be provided.
Override - Parcel Holds7/28/20081/1/19007/28/2008  
7th floor rough in
INSP-Sprinkler Rough-in/Hydro7/11/20087/14/20087/14/2008ADEFR
DetailsTroy Cobbley
Jeff and I agreed to have Forrest continue the inspections on this project due to agreements on sidewall head placement at the air conditioning units.
PLANS/APPL TAKEN TO FRONT DESK  7/10/2008 DONE
DetailsCathy Brown
Override - Parcel Holds  7/10/2008  
Override - Parcel Holds  7/10/2008  
Permit Ready to Issue  7/10/2008 DONE
DetailsCathy Brown
Telephone call  7/10/2008 DONE
DetailsCathy Brown
tlk to gerald ebeling ###-#### that permit and fees are ready to be picked up
Override - Parcel Holds  7/10/2008  
Issue and Print Permit  7/10/2008 DONE
Inspection Record Card- Fire6/30/2008 7/8/2008 DONE
DetailsCathy Brown
Sprinkler Plan Check6/30/2008 7/8/2008 PASS
Details
Plans are approved by Bryan Johnson
Application received  6/30/2008