Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 8/11/2008 | 8/12/2008 | 8/12/2008 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
Issue and Print Permit | | | 7/18/2008 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 7/1/2008 | | 7/17/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | | | 7/17/2008 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/17/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/17/2008 | | 7/17/2008 | | DONE |
|
|
|
|
Telephone call | | | 7/17/2008 | | DONE |
|
|
|
t/c w darcy holmes at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/17/2008 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/15/2008 | | |
|
|
|
received "3" sets of plans & fire alarm app (2) pages & fire alarm submittal (7) pages with each set --took plans to Stephanie Cobbley
|
Alarm Plan Check | | | 7/7/2008 | | FAIL |
|
|
|
does not qualify for quick permit. Need riser, floorplans, and battery calcs
|
Alarm Plan Check | 7/3/2008 | | 7/3/2008 | | FAIL |
Sam Rogers
|
|
|
7/2/08 - Quick permit. Incomplete description of work and no plans included. Called applicant, High Country Alarms, left message. 7/3/03 spoke with Darcey at High Country Alarms, to clarify extent of work. They installed this system, (FIR 07-00933, finaled 5/13/08) but it was found in trouble by the Fire Inspector at a recent sprinkler inspection. Darcey said it is because the 3 remote annunciator panels are pulling too much system current. They therfore want to remove one of the three remote annunciator panels from the system, but the panels are also being used as facp extenders for monitoring initiating points; therefore they will need to make system wiring modifications. I requested they re-submit plans of the system, including the 1-line diagram, clouding what they plan to remove and showing proposed wiring modifications, along with revised battery calculations, as is required for all alarm permits.
|
Application received | | | 7/1/2008 | | |
|
|
|
|