Permit NumberFIR08-00464
StatusFinaled
Name HIGH COUNTRY ALARM INC
Site Address 5556 S FEDERAL WAY
Project NameGUERDON ENTERPRISES TI
Customer Number 
ePlanReview 
Description
This fire alarm permit is to remove a non-required annunciator located at the dry sprinkler system riser that is causing the existing fire alarm panel to be in 'trouble' status.

There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/11/2009 DONE
Plans taken to records to scan
INSP-Final Inspection8/11/20088/12/20088/12/2008PPASS
DetailsTroy Cobbley
permit finaled
Issue and Print Permit  7/18/2008 DONE
Plan assigned to (Stephanie)7/1/2008 7/17/2008 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check  7/17/2008 PASS
PLANS/APPL TAKEN TO FRONT DESK  7/17/2008 DONE
Inspection Record Card- Fire7/17/2008 7/17/2008 DONE
Details
Telephone call  7/17/2008 DONE
Details
t/c w darcy holmes at ###-#### - permit ready and fees given
Permit Ready to Issue  7/17/2008 DONE
Details
Plan resubmittals received  7/15/2008  
received "3" sets of plans & fire alarm app (2) pages & fire alarm submittal (7) pages with each set --took plans to Stephanie Cobbley
Alarm Plan Check  7/7/2008 FAIL
does not qualify for quick permit. Need riser, floorplans, and battery calcs
Alarm Plan Check7/3/2008 7/3/2008 FAIL
DetailsSam Rogers
7/2/08 - Quick permit. Incomplete description of work and no plans included. Called applicant, High Country Alarms, left message. 7/3/03 spoke with Darcey at High Country Alarms, to clarify extent of work. They installed this system, (FIR 07-00933, finaled 5/13/08) but it was found in trouble by the Fire Inspector at a recent sprinkler inspection. Darcey said it is because the 3 remote annunciator panels are pulling too much system current. They therfore want to remove one of the three remote annunciator panels from the system, but the panels are also being used as facp extenders for monitoring initiating points; therefore they will need to make system wiring modifications. I requested they re-submit plans of the system, including the 1-line diagram, clouding what they plan to remove and showing proposed wiring modifications, along with revised battery calculations, as is required for all alarm permits.
Application received  7/1/2008