Permit Information
Permit NumberFIR08-00491
StatusFinaled
Name VIKING AUTOMATIC SPRINKLER CO
Site Address 1301 N ORCHARD ST
Project NameCENTER POINTE ONE
Customer Number 
ePlanReview 
Description
Revised FIR Work Scope: Revision (A) Dated 08/13/08 - The Fire Sprinkler will be adding a new 3” Wilkins back flow preventer devise to the existing riser. New calculations have been provided. A total of 14 heads flowing in the remote area were affected. FIR Work Scope: The Fire Sprinkler scope consists of adding and relocating 67 heads on the 1st and 2nd levels to accommodate a new wall lay out. Calculations were submitted as the modification did appear to affect the remote area of operation. The existing FDC and Wall PI valve are also being modified. The modification consist of relocating them both to a new out side wall. The new location is relatively the same as it was originally installed. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-02372.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/13/2010 DONE
Sent to records for scanning.
INSP-Final Inspection6/25/20096/30/20096/30/2009APASS
DetailsTroy Cobbley
Permit finaled. The forward flush passed.
INSP-Final Inspection3/4/20093/5/20093/5/2009AFAIL
DetailsTroy Cobbley
This permit will be ok to final when the fire alarm interconnects have been verified.
INSP-Sprinkler Rough-in/Hydro2/17/20092/18/20092/18/2009PPASS
DetailsTroy Cobbley
The above ground hydo test for the new east addition passed.
Override - Parcel Holds2/17/20091/1/19002/17/2009  
sprinkler only
INSP-Sprinkler Rough-in/Hydro2/10/20092/11/20092/11/2009APASS
DetailsTroy Cobbley
Underground flush passed. See city approved plans for locations of sidewalls in entrance pockets are ok to cover
Override - Parcel Holds2/10/20091/1/19002/10/2009  
flush inspection
INSP-Sprinkler Rough-in1/27/20091/28/20091/28/2009APASS
DetailsTroy Cobbley
See the city approved plans for the sprinkler piping on the first floor, at the entry lobby, that can be covered. It has todays date 1/28/2009.
Override - Parcel Holds1/27/20091/1/19001/27/2009  
this for fire only
CHANGE STATUS TO (ISS)  1/16/2009 DONE
DetailsAlexandra L. DeYoung
Case Summary  1/16/2009 DONE
Sprinkler Plan Check1/14/2009 1/14/2009 PASS
DetailsTim Frost
See attached comments
There are NO annotations on the plans
PLANS/APPL TAKEN TO FRONT DESK  1/14/2009 DONE
Override - Parcel Holds  1/14/2009  
Inspection Record Card- Fire1/14/2009 1/14/2009 DONE
DetailsCathy Brown
Telephone call  1/14/2009 DONE
DetailsCathy Brown
tlk to tom easton ###-#### that permit and fees are ready to be picked up
Override - Parcel Holds  1/14/2009  
Permit Ready to Issue  1/14/2009 DONE
DetailsCathy Brown
INSP-Sprinkler Rough-in1/12/20091/13/20091/13/2009APASS
DetailsTroy Cobbley
The north east facing canopy can be covered.
Plan assigned to (SAM)1/12/2009 1/12/2009 DONE
DetailsBarbara Stitt
Plan resubmittals received  1/12/2009 DONE
Override - Parcel Holds  1/12/2009  
INSP-Sprinkler Rough-in1/8/20091/9/20091/9/2009APASS
DetailsTroy Cobbley
The two east side outside canopies are ok to cover.
Override - Parcel Holds1/8/20091/1/19001/8/2009  
r/i inspection
INSP-Sprinkler Rough-in1/6/20091/6/20091/6/2009PPASS
DetailsTroy Cobbley
The sprinkler piping in the upper level of the new east entry lobby can be covered. Plan resubmittals are required showing the piping changes. I spoke to Tom with Viking about this.
Override - Parcel Holds  1/6/2009  
INSP-Supply line flush12/8/200812/9/200812/9/2008APASS
DetailsTroy Cobbley
This inspection was actually for an underground hydro not an underground flush. The hydro test passed.
Miscellaneous action  11/20/2008 DONE
Approved contractor's request to install dry sidewall (DSW) sprinklers in a cold concealed space, in excess of the maximum listed distance below the floor joists. Due to practical difficulties presented by the construction, and the relatively small area (156 sf) and shallow depth (24") of the concealed space, it will be approved to install the DSW heads with the deflectors at 8" below the floor joists." (ref. IFC 104.8)
INSP-Sprinkler Rough-in/Hydro10/10/200810/13/200810/13/2008PPASS
DetailsTroy Cobbley
See the city approved plans with todays date for locations where the sprinkler piping can be covered.
INSP-Sprinkler Rough-in/Hydro10/9/200810/9/200810/9/2008PFAIL
DetailsForrest France
Trapeeze hangers at the lower level branch lines in the south office and delivery rooms are not approved (sidewinder sammys in the narrow dimention), discussed main and branchline changes to be shown on resubmittals prior to project final. See stamped plan set for location inspected today.
INSP-Sprinkler Rough-in8/21/20088/22/20088/22/2008PPASS
DetailsTroy Cobbley
This inspection was for the underground supply cover. The two 45 elbows have been replaced with a single 90 elbow. The piping is approved for cover.
PLANS/APPL TAKEN TO FRONT DESK  8/22/2008 DONE
Details
Inspection Record Card- Fire8/22/2008 8/22/2008 DONE
Details
Telephone call  8/22/2008 DONE
Details
left vm for tom easton at ###-#### - permit ready and fees given
Permit Ready to Issue  8/22/2008 DONE
Details
CHANGE STATUS TO (ISS)  8/22/2008 DONE
DetailsTisha Gallop
picked up plan mod
(F) Reprint permit  8/22/2008 DONE
DetailsTisha Gallop
Sprinkler Plan Check8/13/2008 8/20/2008 PASS
Details
plans are approved
Plan resubmittals received  8/13/2008 DONE
Received 5 sets of resubmittal plans stamped plans and sent to fire
Plan assigned to (OutSourced)8/11/2008 8/11/2008 DONE
DetailsCathy Brown
Sprinkler Plan Check7/31/2008 8/7/2008 FAIL
Details
These plans were denied do to lack of or missing information. Upon request, the denied set of plans my be retrieved from my office for salvage. The denied set of plans will be maintained for five working days
Plan resubmittals received  7/31/2008  
received fire spr app, united water sheet, fire spr ungrade (8) pages--"5" sets of plans- put plans on fire shelf
Issue and Print Permit  7/28/2008  
Inspection Record Card- Fire7/25/2008 7/25/2008 DONE
Details
PLANS/APPL TAKEN TO FRONT DESK  7/25/2008 DONE
Details
Telephone call  7/25/2008 DONE
Details
left vm for tom easton at ###-#### - permit ready and fees given
Permit Ready to Issue  7/25/2008 DONE
Details
Sprinkler Plan Check7/11/2008 7/24/2008 PASS
Details
plans are approved
Application received  7/11/2008  
Pending Assignment by SAM7/11/2008 7/11/2008 DONE
DetailsTim Frost
Case Summary  7/11/2008 DONE
Plan assigned to (SAM)7/11/2008    
Plan resubmittals received     
DetailsSam Rogers