Permit Information
Permit NumberFIR08-00500
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1122 N LIBERTY RD
Project NameApollo College
Customer Number 
ePlanReview 
Description
10/10/08 Plan Review:
These plans were resubmitted with corrected node points for review. Each of the 4 hydraulically most demanding remote area calculation summaries were also submitted for review in order to verify the modifications made in the field during construction did not adversely affect the system as it was originally designed. Those revisions were noted as Rev 1, 2 & 3 with a revision date of 09/12/08.
FIR OH Scope:
Beginning from an existing 6” supply located with in the riser room at the NW corner of the building; install a 3” wet riser to serve through out the entire structure over the first and second floors including the exterior balconies. The fire sprinkler system work shall comply with the IFC 2006, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD08-00234 & UG permit FIR08-00290.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  3/10/2009 DONE
Sent for archiving
INSP-Final Inspection1/8/20091/9/20091/9/2009APASS
DetailsTroy Cobbley
Permit finaled. Forward flush also passed.
INSP-Sprinkler Rough-in/Hydro12/15/200812/16/200812/16/2008PPASS
DetailsTroy Cobbley
The remaining hydro tests passed.
INSP-Sprinkler Rough-in/Hydro12/8/200812/9/200812/9/2008APASS
DetailsTroy Cobbley
The second floor hydro test passed. The first floor hydro test failed.
INSP-Sprinkler Rough-in12/3/200812/4/200812/4/2008PPASS
DetailsTroy Cobbley
See the city approved plans for the deficiencies that have been corrected on the first and second floors. I pointed out to Charles that the FDC is possibly located too close to the roof rain gutter and side of the building.
INSP-Sprinkler Rough-in11/20/200811/21/200811/21/2008PFAIL
DetailsForrest France
See red lines on plan set for areas in need of correction (2nd floor only inspected today) including an obstructed head at a janitors room, one missing arm-over hanger, heads overspaced at the restrooms, six overspaced heads at the southeast lounge room.
INSP-Sprinkler Rough-in10/15/200810/20/200810/20/2008APART
DetailsTroy Cobbley
See the city approved plans for the locations of the defieciencies. Only the rooms on the first floor that do not have red correction marks in them can be covered. No rooms on the second floor can be covered. As-builts need to be provided prior to a final inspection which show all of the changes as marked on the city approved plans.
Issue and Print Permit  10/15/2008 DONE
Sprinkler Plan Check10/3/2008 10/14/2008 PASS
Details
These modified plans and calculation are approved. A total of 42 heads in the 4 hydraulically most demanding remote area's that were affected as a result of the of the plan and calculation modifications. Plans are approved by Bryan Johnson
PLANS/APPL TAKEN TO FRONT DESK  10/14/2008 PASS
DetailsCathy Brown
Inspection Record Card- Fire10/14/2008 10/14/2008 DONE
DetailsCathy Brown
Telephone call  10/14/2008 DONE
DetailsCathy Brown
lft ms with recepectionist for lily ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  10/14/2008 DONE
DetailsCathy Brown
Plan resubmittals received  10/3/2008  
received 5 apps , 5 information books,and 5 copies of sheets 1,2,3,of 3 gave plans to Ken
Plan resubmittals received  10/2/2008 DONE
Sprinkler Plan Check9/15/2008 9/27/2008 FAIL
Details
These plans were denied. The plan reviewer could not verify the calculation node points due to clarity.
Upon request, the denied set of plans may be retrieved from my office for salvage. The denied set will be maintained for 5 working days
Plan resubmittals received  9/15/2008 DONE
received 5 sets of resubmittal plans and books stamped and put in fire box///dld
Sprinkler Plan Check7/16/2008 7/29/2008 FAIL
Details
These plans were denied due to missing or lack of information. Upon request the denied set of plans may be retrieved from my office for salvage. The denied set of plans will be maintained for 5 working days
Early Start  7/18/2008 DONE
Early start request approved. Doc attached.
Case Summary  7/16/2008  
Application received  7/16/2008  
Pending Assignment by SAM7/16/2008