Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 10/17/2008 | 10/17/2008 | 10/17/2008 | P | PASS |
Forrest France
|
|
|
Repairs are complete, final fire alarm testing passed, permit finaled.
|
INSP-Final Inspection | 10/13/2008 | 10/14/2008 | 10/14/2008 | A | FAIL |
Forrest France
|
|
|
PIV tamper is not correctly adjusted, waterflow switch is not functional, noted ground fault at the panel after testing had started, inspection concluded until repairs are made.
|
Issue and Print Permit | | | 8/8/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 8/4/2008 | | 8/4/2008 | | DONE |
|
|
|
|
Telephone call | | | 8/4/2008 | | DONE |
|
|
|
left message w lisa for jason minnick at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 8/4/2008 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 7/28/2008 | | 7/31/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | | | 7/31/2008 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/31/2008 | | DONE |
|
|
|
|
Plan resubmittals received | | | 7/28/2008 | | |
|
|
|
received fire alarm application & "3" sets of plans-- took plans to stephanie c.
|
Plan assigned to (Stephanie) | 7/17/2008 | | 7/24/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Telephone call | | | 7/24/2008 | | DONE |
|
|
|
Spoke to Jason at Audio Electronics to verify that there is a dry system in addition to the wet sprinkler system due to only one valve being shown for the dry system pressure switch, and none of the other required valves were shown. He verified there is a dry system. I let him know I would have to deny the plans.
|
Alarm Plan Check | | | 7/24/2008 | | FAIL |
|
|
|
See review comments
|
Miscellaneous action | | | 7/24/2008 | | DONE |
|
|
|
I faxed the review comments for the failed plans to Audio Electronics
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/24/2008 | | DONE |
|
|
|
Failed plans put in the drawer for contractor to pick up.
|
Case Summary | | | 7/17/2008 | | DONE |
Marsha Smylie
|
|
|
|
Application received | | | 7/17/2008 | | |
Marsha Smylie
|
|
|
|