Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 10/20/2008 | 10/21/2008 | 10/21/2008 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
Miscellaneous action | | | 10/17/2008 | | DONE |
|
|
|
Spoke with Sam, Troy, and Mountain Alarm regarding system smoke detectors versus standalone smoke alarms. Per Sam, it is okay to install system smoke detectors in place of the stand alone alarms in this building provided the locations meet the R4 requirements of NFPA 72. In addition, it is acceptable for all system smoke detectors (common areas as well as in-room) to signal the system alarm. The notes placed on the review comments regarding the single-station/multi-station alarms were an error on my part.
|
INSP-Final Inspection | 9/26/2008 | 9/29/2008 | 9/29/2008 | P | FAIL |
Troy Cobbley
|
|
|
Verify phone lines, provide knox box, provide tamper switches, provide map at the facp, provide the 110v smoke alarms and provide the correct size batteries. No items were tested except for the phone line troubles. See the city approved plans for a complete list of deficiencies.
|
Plan assigned to (Stephanie) | 7/17/2008 | | 7/24/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | | | 7/24/2008 | | PASS |
|
|
|
see redlines on drawings and review comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/24/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/24/2008 | | 7/24/2008 | | DONE |
|
|
|
|
Telephone call | | | 7/24/2008 | | DONE |
|
|
|
left message w diane for bret anderson at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/24/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/24/2008 | | DONE |
|
|
|
|
Case Summary | | | 7/17/2008 | | DONE |
|
|
|
|
Application received | | | 7/17/2008 | | |
|
|
|
|