Permit Information
Permit NumberFIR08-00510
StatusFinaled
Name MOUNTAIN ALARM
Site Address 11359 W TIOGA ST
Project NameASPEN RIDGE WEST RESIDENTIAL
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a new automatic and manual fire alarm system with sprinkler system monitoring in an existing residential care facility. The manual system is required per health and welfare.

Associated building permit: BLD08-00833 This project is for the placement of interior non bearing partitions to add three bedrooms to an existing single family dwelling. The family room will be divided to create 2-bedrooms (#2) & (#3) and the rear sitting room will have partitions to create a bedroom (# 7) and a small conference room that must be open to the hallway off of the dining room; adding 3-wall sections into the garage area to extend the garage hall and add a closet to bedroom # 6. Separate electrical and mechanical permits are required. This plan review is done under the Planning and Development Services Building Division Policy citing the IBC section 310.1 for R-4 occupancies affected March 20, 2008. R-1A zoning approved by Colleen Carroll. All per the approved plans as marked and the plan review notes. pep

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/11/2009 DONE
Plans taken to records to scan
INSP-Final Inspection10/20/200810/21/200810/21/2008PPASS
DetailsTroy Cobbley
permit finaled
Miscellaneous action  10/17/2008 DONE
Spoke with Sam, Troy, and Mountain Alarm regarding system smoke detectors versus standalone smoke alarms. Per Sam, it is okay to install system smoke detectors in place of the stand alone alarms in this building provided the locations meet the R4 requirements of NFPA 72. In addition, it is acceptable for all system smoke detectors (common areas as well as in-room) to signal the system alarm. The notes placed on the review comments regarding the single-station/multi-station alarms were an error on my part.
INSP-Final Inspection9/26/20089/29/20089/29/2008PFAIL
DetailsTroy Cobbley
Verify phone lines, provide knox box, provide tamper switches, provide map at the facp, provide the 110v smoke alarms and provide the correct size batteries. No items were tested except for the phone line troubles. See the city approved plans for a complete list of deficiencies.
Plan assigned to (Stephanie)7/17/2008 7/24/2008 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check  7/24/2008 PASS
see redlines on drawings and review comments
PLANS/APPL TAKEN TO FRONT DESK  7/24/2008 DONE
Inspection Record Card- Fire7/24/2008 7/24/2008 DONE
Details
Telephone call  7/24/2008 DONE
Details
left message w diane for bret anderson at ###-#### - permit ready and fees given
Permit Ready to Issue  7/24/2008 DONE
Details
Issue and Print Permit  7/24/2008 DONE
Case Summary  7/17/2008 DONE
Application received  7/17/2008