Miscellaneous action | | | 7/17/2009 | | DONE |
|
|
|
Taken to records for scanning.
|
INSP-Final Inspection | 6/10/2009 | 6/11/2009 | 6/11/2009 | A | PASS |
Forrest France
|
|
|
Corrections completed, fire alarm work passed final inspection.
|
INSP-Final Inspection | 6/8/2009 | 6/9/2009 | 6/9/2009 | P | FAIL |
Forrest France
|
|
|
Operation of the smoke detector at the tool failed to initiate shunt trip power switch. Sprinkler tamper switch tested okay.
|
INSP-Conference | 1/26/2009 | 1/26/2009 | 2/2/2009 | P | DONE |
Forrest France
|
|
|
|
FIR-Aging Inspection | 11/6/2008 | 11/6/2008 | 11/6/2008 | | DONE |
Forrest France
|
|
|
Work in progress
|
Inspection Record Card- Fire | 8/6/2008 | | 8/6/2008 | | DONE |
|
|
|
|
Telephone call | | | 8/6/2008 | | DONE |
|
|
|
t/c w andy sellers at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 8/6/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 8/6/2008 | | DONE |
|
|
|
|
Plan assigned to (Stephanie) | 7/18/2008 | | 8/5/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | | | 8/5/2008 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/5/2008 | | DONE |
|
|
|
|
Miscellaneous action | | | 8/4/2008 | | DONE |
|
|
|
Information requested received
|
Telephone call | | | 7/24/2008 | | DONE |
|
|
|
Left a message for Andy letting him know that I need the information discussed by Monday, the 28th, I would need to deny the plans and have him resubmit.
|
Telephone call | | | 7/21/2008 | | DONE |
|
|
|
Spoke with Andy and asked him to provide a new riser and floorplan layout clouding the new devices. The current plans have several initiating devices clouded, but not all of them pertain to this permit scope. In addition, the permit app. gives a PE as the designer, therefore I asked Andy for a letter from the Engineer per Boise City Policy. Andy stated that he thought the 'designer' needed to be the original engineer. I clarified that the engineer is only to be listed as the 'designer' if he/she signs off on them that the drawings did not change for the original bid documents. If someone changed the engineer's design, then that person must be NICET certified or factory trained, and that it is that person that must be listed as the 'designer' on the permit app. He said he would get the information to me within a day or two.
|
Application received | | | 7/18/2008 | | |
|
|
|
|