Miscellaneous action | | | 5/11/2009 | | DONE |
|
|
|
Plans taken to records to scan
|
INSP-Final Inspection | 1/8/2009 | 1/9/2009 | 1/9/2009 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 1/7/2009 | 1/8/2009 | 1/8/2009 | A | FAIL |
Troy Cobbley
|
|
|
Lower the 110 cd strobe in the storage area, install the existing smoke detector that is over the facp to the deck, provide the missing strobe in the east storage area and retest all of the audio/visual devices.
|
INSP-Final Inspection | 1/6/2009 | 1/7/2009 | 1/7/2009 | A | CANC |
Troy Cobbley
|
|
|
The hood suppression system has not been tied into the fire alarm system so no inspection was performed.
|
INSP-Final Inspection | 7/31/2008 | 8/1/2008 | 8/1/2008 | A | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
|
INSP-Final Inspection | 7/30/2008 | 7/31/2008 | 7/31/2008 | P | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
|
INSP-Final Inspection | 7/29/2008 | 7/30/2008 | 7/30/2008 | P | CANC |
Troy Cobbley
|
|
|
Phone #: ###-#### Internet Inspection Request from: Diane Turner Inspection cancelled from web by: Diane Turner
|
Plan assigned to (Stephanie) | 7/28/2008 | | 7/29/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Alarm Plan Check | | | 7/29/2008 | | PASS |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/29/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 7/29/2008 | | 7/29/2008 | | DONE |
|
|
|
|
Telephone call | | | 7/29/2008 | | DONE |
|
|
|
t/c w bret anderson at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 7/29/2008 | | DONE |
|
|
|
|
Issue and Print Permit | | | 7/29/2008 | | DONE |
Tisha Gallop
|
|
|
|
Plan resubmittals received | | | 7/28/2008 | | |
Stephanie L. Cobbley
|
|
|
Received application and two copies of submittal folders and sheets FA-1, FA-2; taken to Fire review
|
Plan assigned to (Stephanie) | 7/21/2008 | | 7/25/2008 | | DONE |
Stephanie L. Cobbley
|
|
|
|
Early Start | | | 7/25/2008 | | DONE |
|
|
|
Approved Early Start request. Doc attached.
|
Alarm Plan Check | | | 7/25/2008 | | FAIL |
|
|
|
See redlined drawings and review comments.
|
Miscellaneous action | | | 7/25/2008 | | DONE |
|
|
|
Faxed the review comments to Bret Anderson
|
PLANS/APPL TAKEN TO FRONT DESK | | | 7/25/2008 | | DONE |
|
|
|
Redlined plans ready for contractor pick-up at front counter
|
Miscellaneous action | | | 7/25/2008 | | DONE |
Tisha Gallop
|
|
|
picked up denied plans
|
Case Summary | | | 7/21/2008 | | DONE |
|
|
|
|
Application received | | | 7/21/2008 | | |
|
|
|
|