Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR08-00529
StatusFinaled
Name ALLIED GENERAL FIRE & SECURITY
Site Address 5369 W IRVING ST
Project NameSIMPLOT BUILDING B
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace the existing fire alarm control panel with a new one because the existing panel will not support the addition of hood suppression system monitoring. This permit scope also includes monitoring existing duct detector, sprinkler system, Fenwal system, and Ansul system monitoring devices.
There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Miscellaneous action  5/11/2009 DONE
Plans taken to records to scan
INSP-Final Inspection9/16/20089/17/20089/17/2008APASS
DetailsTroy Cobbley
Fire alarm testing completed, all repairs made per last inspection. KR
INSP-Final Inspection9/15/20089/15/20089/15/2008PFAIL
DetailsTroy Cobbley
The alarm signals are silencing and restoring themselves. The phone lines and battery signals are ok.
INSP-Final Inspection9/9/20089/9/20089/9/2008PFAIL
DetailsTroy Cobbley
There were no approved plans on site and after a discussion with the technician a resubmittal is in order due to the reconfiguration of the initiation devices into the new fire alarm panel. They had been submitted as reporting to the addressable loop but are not utilizing the hardwired zones.
Plan assigned to (Stephanie)7/24/2008 7/31/2008 DONE
DetailsStephanie L. Cobbley
Alarm Plan Check  7/31/2008 PASS
PLANS/APPL TAKEN TO FRONT DESK  7/31/2008 DONE
Inspection Record Card- Fire7/31/2008 7/31/2008 DONE
Details
Telephone call  7/31/2008 DONE
Details
left vm for ken webster at ###-#### - permit ready and fees given
Permit Ready to Issue  7/31/2008 DONE
Details
Issue and Print Permit  7/31/2008 DONE
Issue and Print Permit  7/31/2008 DONE
Application received  7/24/2008