Miscellaneous action | | | 3/10/2009 | | DONE |
|
|
|
Sending for archiving
|
INSP-Final Inspection | 1/21/2009 | 1/22/2009 | 1/22/2009 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 1/21/2009 | 1/21/2009 | 1/21/2009 | P | FAIL |
Troy Cobbley
|
|
|
The forward flush passed. Bruce needs to change the mixed temperature pendants to be all 155 degree except in locations as required
|
INSP-Final Inspection | 1/15/2009 | 1/16/2009 | 1/16/2009 | P | CANC |
Troy Cobbley
|
|
|
The project related fire alarm is not complete so bruce and I agreed to reschedule for next week.
|
Override - Parcel Holds | 1/15/2009 | 1/1/1900 | 1/15/2009 | | |
|
|
|
does not apply
|
INSP-Sprinkler Rough-in | 10/24/2008 | 10/24/2008 | 10/24/2008 | P | PASS |
Troy Cobbley
|
|
|
The overhead sprinkler piping can be covered.
|
Issue and Print Permit | | | 10/24/2008 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/20/2008 | | DONE |
|
|
|
|
Telephone call | | | 10/20/2008 | | DONE |
|
|
|
t/c w brook nelson at ###-#### - permit ready and fees given
|
Permit Ready to Issue | | | 10/20/2008 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/20/2008 | | 10/20/2008 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/8/2008 | | 10/19/2008 | | PASS |
|
|
|
plans are approved - Note: This was the third review of these modified plans and calculations. A total of 34 heads over 3 remote areas of operation were affected as a result of this review.
|
Plan resubmittals received | | | 10/8/2008 | | |
|
|
|
Received three copies of application, submittal info and plan sheets 1 of 2, 2 of 2; taken to Fire review
|
Sprinkler Plan Check | 9/15/2008 | | 9/29/2008 | | FAIL |
|
|
|
These plans were denied due to lack of revision notes or references. Upon request, the denied set of plans may be retrieved for salvage. The denied set of plans will be maintained for 5 working days.
|
Plan resubmittals received | | | 9/15/2008 | | |
Tisha Gallop
|
|
|
Plan Modification: Received four copies of application, submittal information, and sheet 1 of 2, 2 of 2; taken to fire review
|
INSP-Sprinkler Rough-in | 8/28/2008 | 8/29/2008 | 8/29/2008 | A | PART |
Troy Cobbley
|
|
|
The above ground hydro test passed but the rough-in inspection failed due to cpvc piping being installed under the mezzanine instead of the steel piping as per the plans and hydraulic calculations.
|
INSP-Sprinkler Rough-in/Hydro | 8/28/2008 | 8/28/2008 | 8/28/2008 | P | PASS |
Troy Cobbley
|
|
|
The underground flush passed.
|
Issue and Print Permit | | | 8/13/2008 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/11/2008 | | DONE |
Cathy Brown
|
|
|
|
Inspection Record Card- Fire | 8/11/2008 | | 8/11/2008 | | DONE |
Cathy Brown
|
|
|
|
Telephone call | | | 8/11/2008 | | DONE |
Cathy Brown
|
|
|
tlk to brook nelson ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 8/11/2008 | | DONE |
Cathy Brown
|
|
|
|
Sprinkler Plan Check | 7/30/2008 | | 8/9/2008 | | PASS |
|
|
|
Plans & Calculations are approved by Bryan Johnson
|
Early Start | | | 8/5/2008 | | DONE |
|
|
|
Approved Early start request to install sprinkler piping only below the mezanine. Doc attached.
|
Application received | | | 7/30/2008 | | |
|
|
|
|
Pending Assignment by SAM | 7/30/2008 | | | | |
Sam Rogers
|
|
|
|
Plan assigned to (SAM) | 7/30/2008 | | | | |
|
|
|
|
Plan assigned to (SAM) | 9/15/2008 | | | | |
Sam Rogers
|
|
|
|